Sale!

Ducted Split System – Advance R32

£1,695.75 - £2,680.05 ex. VAT

Clear

Note: All systems must be installed by Certified Installer.

Description

Indoor UnitsSingle Phase3 Phase
FBA71A9FBA100AFBA125AFBA140AFBA100AFBA125AFBA140A
CapacityUK Total Cooling kW7,7610,8013,6014,9010,8013,6014,90
UK Sensible Cooling kW5,327,449,3010,257,449,3010,25
Nominal Cooling kW6,89,512,113,49,512,113,4
Nominal Heating kW7,510,813,515,510,813,515,5
Seasonal Efficiency (EN14825) COOLINGEnergy LabelA++A+A+
PdesignkW6,89,512,113,49,512,113,4
SEER6,195,835,275,815,835,275,81
Annual Energy Consumption  kWh3855701378138457013781384
Seasonal Efficiency (EN14825) HEATINGEnergy LabelA+AA
PdesignkW4,56,06,07,86,06,07,8
SCOP4,013,853,633,853,853,633,85
Annual Energy Consumption kWh1571218223142836218223142836
Nominal EfficiencyEER/COP3.60/3.893.20/4.772.61/4.012.81/3.983.20/4.772.61/4.012.81/3.98
Air Flow Rate (Cooling)High / Nom / Lowm3/sec0.300/0.250/0.2080.483/0.433/0.3830.566/0.483/0.3910.566/0.483/0.3910.483/0.433/0.3830.566/0.483/0.3910.566/0.483/0.391
External Static PressureHigh / NomPa150/30150/40150/50150/50150/40150/50150/50
DimensionsHeightmm245245245245245245245
Widthmm1000140014001400140014001400
Depthmm800800800800800800800
Weightkg35464646464646
Sound Pressure (Cooling)High/Nom/LowdBA30/28/2534/32/3037/35/3237/35/3234/32/3037/35/3237/35/32
Sound Pressure (Heating)High/Nom/LowdBA31/28/2536/33/3038/35/3238/35/3236/33/3038/35/3238/35/32
Sound Power (Cooling)dBA56586262586262
Outdoor UnitsRZASG71MV1RZASG100MV1RZASG125MV1RZASG140MV1RZASG100MY1RZASG125MY1RZASG140MY1
Dimensions HeightxWidthxDepth mm770 x 900 x 320990 x 940 x 320990 x 940 x 320990 x 940 x 320990 x 940 x 320990 x 940 x 320990 x 940 x 320
Weight kg60707078707077
Electrical DetailsPower Supply1ph1ph1ph1ph3ph3ph3ph
Running CurrentA17,521,828,327,614,615,115,1
Max Fuse SizeA20253232161616
Interconnection Wiring Core / Cable Size3+E / 1.53+E / 1.5
Piping Connections Liquid / Gasinches (mm)3/8 (9.5) / 5/8 (15.9)3/8 (9.5) / 5/8 (15.9)
PipeworkMaximum Lengthm50505050505050
Maximum Vertical Risem30303030303030
Precharged tom30303030303030
Additional chargeg/mRefer to Installation ManualRefer to Installation Manual
Holding chargekg2,452,602,602,902,602,602,90
Sound Pressure (Cooling)    Nom/Night QuietdBA46/4253/4453/4454/4453/4453/4454/44
Sound Pressure (Heating)    Nom/Night QuietdBA47/4257/4457/4457/4457/4457/4457/44
Sound Power (Cooling)dBA65707173707173
Operating Range (Cooling) Min / Max°CDB-15/46-15/46-15/46-15/46-15/46-15/46-15/46
Operating Range (Heating) Min / Max°CWB-15/15.5-15/15.5-15/15.5-15/15.5-15/15.5-15/15.5-15/15.5
Air Flow Rate (Cooling) Nominalm3/sec0,9331,1501,1831,2661,1501,1831,266