Indoor UnitsSingle Phase3 Phase
FBA71A9FBA100AFBA125AFBA140AFBA100AFBA125AFBA140A
CapacityUK Total Cooling kW7,7610,8013,6014,9010,8013,6014,90
UK Sensible Cooling kW5,327,449,3010,257,449,3010,25
Nominal Cooling kW6,89,512,113,49,512,113,4
Nominal Heating kW7,510,813,515,510,813,515,5
Seasonal Efficiency (EN14825) COOLINGEnergy LabelAAA
PdesignkW6,89,512,113,09,512,113,0
SEER5,575,254,855,505,254,855,50
Annual Energy Consumption  kWh4276331497141863314971418
Seasonal Efficiency (EN14825) HEATINGEnergy LabelAAA
PdesignkW4,56,06,07,86,06,07,8
SCOP3,813,813,553,853,813,553,85
Annual Energy Consumption  kWh1654220523662836220523662836
Nominal EfficiencyEER/COP3.60/3.733.20/4.772.30/4.012.72/3.983.20/4.772.30/4.012.72/3.98
Air Flow Rate (Cooling)High/Nom/Lowm3/sec0.300/0.250/0.2080.483/0.433/0.3830.566/0.483/0.3910.566/0.483/0.3910.483/0.433/0.3830.566/0.483/0.3910.566/0.483/0.391
External Static PressureHigh/NomPa150/30150/40150/50150/50150/40150/50150/50
DimensionsHeightmm245245245245245245245
Widthmm1000140014001400140014001400
Depthmm800800800800800800800
Weightkg35464646464646
Sound Pressure (Cooling)High/Nom/LowdBA30/28/2534/32/3037/35/3237/35/3234/32/3037/35/3237/35/32
Sound Pressure (Heating)High/Nom/LowdBA31/28/2536/33/3038/35/3238/35/3236/33/3038/35/3238/35/32
Sound Power (Cooling)dBA56586262586262
Outdoor UnitsAZAS71MV1AZAS100MV1AZAS125MV1AZAS140MV1AZAS100MY1AZAS125MY1AZAS140MY1
Dimensions HeightxWidthxDepthmm770 x 900 x 320990 x 940 x 320990 x 940 x 320990 x 940 x 320990 x 940 x 320990 x 940 x 320990 x 940 x 320
Weightkg60707078707077
Electrical DetailsPower Supply1ph1ph1ph1ph3ph3ph3ph
Running CurrentA17,521,828,327,614,615,115,1
Max Fuse SizeA20253232161616
Interconnection Wiring Core / Cable Size3+E / 1.53+E / 1.5
Piping Connections Liquid / Gasinches (mm)3/8 (9.5) / 5/8 (15.9)3/8 (9.5) / 5/8 (15.9)
PipeworkMaximum Lengthm30303030303030
Maximum Vertical Risem30303030303030
Precharged tom30303030303030
Additional chargeg/mRefer to Installation ManualRefer to Installation Manual
Holding chargekg2,452,602,602,902,602,602,90
Sound Pressure (Cooling)    Nom/Night QuietdBA46/4253/4453/4454/4453/4453/4454/44
Sound Pressure (Heating)    Nom/Night QuietdBA47/4257/4457/4457/4457/4457/4457/44
Sound Power (Cooling)dBA65707173707173
Operating Range (Cooling) Min/Max°CDB-5/46-5/46-5/46-5/46-5/46-5/46-5/46
Operating Range (Heating) Min/Max°CWB-15/15.5-15/15.5-15/15.5-15/15.5-15/15.5-15/15.5-15/15.5
Air Flow Rate (Cooling) Nominalm3/sec0,9331,1501,1831,2661,1501,1831,266