PLA-SM R410A 4-Way Blow Ceiling Cassette System (3 Phase)

From: £2,059.00£2,563.00


Note: All systems must be installed by Certified Installer.

Description

PLA-SM INDOOR UNITS PLA-SM100EA PLA-SM125EA PLA-SM140EA
CAPACITY (kW) Heating (nominal) 11.2 (2.8-12.5) 13.5 (4.8-15.0) 15.0 (4.9-15.8)
Cooling (nominal) 9.4 (3.7-10.6) 12.1 (5.6-13.0) 13.6 (5.8-14.1)
Heating (UK) 9.63 (2.41-10.75) 11.61 (4.13-12.90) 12.90 (4.21-13.59)
Cooling (UK) 8.55 (3.37-9.65) 11.01 (5.10-11.83) 12.38 (5.28-12.83)
SHF (nominal) 0.77 0.73 0.70
COP / EER (nominal) 3.21 / 2.85 3.41 / 2.85 3.11 / 2.41
SCOP (ƞsh) / SEER (ƞsc) (BS EN14825) 4.10 / 5.70 3.75 (150.1%) / 5.27 (210.6%) 3.76 (150.2%) / 5.25 (210.1%)
ErP ENERGY EFFICIENCY CLASS Heating/Cooling A+ / A+
AIRFLOW (l/s) Lo-Mi1-Mi2-Hi 317-383-433-483 350-417-467-517 400-433-483-533
PIPE SIZE mm (in) Gas/Liquid 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”) 15.88 (5/8”) / 9.52 (3/8”)
SOUND PRESSURE LEVEL (dBA) Lo-Mi1-Mi2-Hi 31-34-37-40 33-37-41-44 36-39-42-44
SOUND POWER LEVEL (dBA) 61 65 65
DIMENSIONS (mm) Width x Depth x Height (Grille) 840(950)x840(950)x298(40) 840(950)x840(950)x298(40) 840(950)x840(950)x298(40)
WEIGHT (kg) Unit / Panel 24 (5) 26 (5) 26 (5)
ELECTRICAL SUPPLY Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit
FUSE RATING (BS88) – HRC (A) 6 6 6
INTERCONNECTING CABLE No. Cores 4 4 4
GRILLE REFERENCE PLP-6EA PLP-6EA PLP-6EA
WIRED REMOTE CONTROLLER REFERENCE PAR-33MAA PAR-33MAA PAR-33MAA
WIRELESS REMOTE CONTROLLER REFERENCE PAR-SL100A-E PAR-SL100A-E PAR-SL100A-E
SUZ-SA / PUHZ-SP OUTDOOR UNITS PUHZ-SP100YKA PUHZ-SP125YKA PUHZ-SP140YKA
SOUND PRESSURE LEVEL (dBA) Heating/Cooling 54 / 51 56 / 54 57 / 58
SOUND POWER LEVEL (dBA) Cooling 70 72 75
WEIGHT (kg) 78 85 85
DIMENSIONS (mm) Width x Depth x Height 1050 x 330 x 981 1050 x 330 x 981 1050 x 330 x 981
ELECTRICAL SUPPLY 380-415v, 50Hz 380-415v, 50Hz 380-415v, 50Hz
PHASE Three Three Three
SYSTEM POWER INPUT (kW) 
Heating (nominal) 3.48 / 3.29 3.95 / 4.23 4.81 / 5.63
Cooling (nominal) 3.13 / 2.73 3.56 / 3.51 4.33 / 4.67
STARTING CURRENT (A) 2.9 4.0 4.0
SYSTEM RUNNING CURRENT (A) Heating/Cooling  [MAX] 5.3 / 5.3 [11.5] 6.8 / 6.4 [11.5] 8.9 / 7.9 [11.5]
FUSE RATING (BS88) – HRC (A) 16 16 16
MAINS CABLE No. Cores 5 5 5
MAX PIPE LENGTH (m) 30 40 40
MAX HEIGHT DIFFERENCE (m) 30 30 30
CHARGE REFRIGERANT (kg) / CO2 EQUIVALENT (t)
R410A (GWP 2088)
3.3 / 6.89 (30m) 3.8 / 7.93 (30m) 3.8 / 7.93 (30m)
MAX ADDITIONAL REFRIGERANT (kg) / CO2 EQUIVALENT (t)
R410A (GWP 2088)
1.2 / 2.51 1.2 / 2.51 1.2 / 2.51

Additional information

PLA-SM R410A 4-Way Blow Ceiling Cassette System (3 Phase)

, ,

Reviews

There are no reviews yet.

Be the first to review “PLA-SM R410A 4-Way Blow Ceiling Cassette System (3 Phase)”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.