Indoor unit | FDE70VG | FDE100VG | FDE100VG | |||
Outdoor unit | FDC71VNP | FDC90VNP | FDC100VNP | |||
Power source | 1 Phase 220-240V, 50Hz / 220V, 60Hz | |||||
Nominal cooling capacity (Min~Max) | kW | 7.1 ( 1.4 ~ 7.1 ) | 9.0 ( 1.9 ~ 9.0 ) | 10.0 ( 2.8 ~ 11.2 ) | ||
Nominal heating capacity (Min~Max) | kW | 7.1 ( 1.0 ~ 7.1 ) | 9.0 ( 1.5 ~ 9.0 ) | 11.2 ( 2.5 ~ 12.5 ) | ||
Power consumption | Cooling/Heating | kW | 2.50 / 1.96 | 2.75 / 2.22 | 2.66 / 2.94 | |
EER/COP | Cooling/Heating | 2.84 / 3.62 | 3.27 / 4.05 | 3.76 / 3.81 | ||
Inrush current | A | 5 | 5 | 5 | ||
Max. current | 14.5 | 18.0 | 21.0 | |||
Sound power level*1 | Indoor*2 | Cooling/Heating | dB(A) | 60 / 60 | 64 / 64 | 64 / 64 |
Outdoor | Cooling/Heating | 67 / 67 | 69 / 69 | 70 / 70 | ||
Sound pressure level*1 2 | Indoor*2 | Cooling (Hi/Me/Lo) | 41 / 37 / 32 | 43 / 38 / 34 | 43 / 38 / 34 | |
Heating (Hi/Me/Lo) | 41 / 37 / 32 | 43 / 38 / 34 | 43 / 38 / 34 | |||
Outdoor | Cooling/Heating | 54 / 54 | 57 / 55 | 57 / 61 | ||
Air flow 2 | Indoor*2 | Cooling (Hi/Me/Lo) | m3/min | 16 / 13 / 10 | 26 / 21 / 16.5 | 26 / 21 / 16.5 |
Heating (Hi/Me/Lo) | 16 / 13 / 10 | 26 / 21 / 16.5 | 26 / 21 / 16.5 | |||
Outdoor | Cooling/Heating | 36 / 36 | 63 / 49.5 | 75 / 79 | ||
Exterior dimensions | Indoor | HeightxWidthxDepth | mm | 210 x 1,320 x 690 | 250 x 1,620 x 690 | |
Outdoor | 640 x 800(+71) x 290 | 750 x 880(+88) x 340 | 845 x 970 x 370 | |||
Net weight | Indoor | kg | 33 | 43 | ||
Outdoor | 45 | 57 | 70 | |||
Ref.piping size | Liquid/Gas | ømm | 6.35(1/4″) / 12.7(1/2″) | 6.35(1/4″) / 15.88(5/8″) | 9.52(3/8″) / 15.88(5/8″) | |
Refrigerant line (one way) length | m | Max.30 | ||||
Vertical height differences | Outdoor is higher/lower | m | Max.20 / Max.20 | |||
Outdoor operating temperature range | Cooling | °C | -15~46*3 | |||
Heating | -15~20 | |||||
Air filter, Q’ty | Pocket Plastic net x2(Washable) | |||||
Remote control (option) | wired:RC-EX3, RC-E5, RCH-E3 wireless:RCN-E-E2 |