SLZ-M R410A 600×600 4-Way Cassette System (Single Phase)

From: £1,086.00£1,509.00


Note: All systems must be installed by Certified Installer.

Description

SLZ-M-FA – INDOOR UNITS SLZ-M25FA SLZ-M35FA SLZ-M50FA SLZ-M60FA
CAPACITY (kW) Heating (nominal) 3.2 (1.3-4.2) 4.0 (1.7-5.0) 5.0 (1.7-6.0) 6.4 (2.5-7.4)
Cooling (nominal) 2.6 (1.5-3.2) 3.5 (1.4-3.9) 4.6 (2.3-5.2) 5.6 (2.3-6.5)
Heating (UK) 2.69 (1.09-3.53) 3.36 (1.43-4.20) 4.20 (1.43-5.04) 5.38 (2.10-6.22)
Cooling (UK) 2.60 (1.50-3.20) 3.46 (1.38-3.86) 4.56 (2.28-5.15) 5.55 (2.28-6.44)
SHF (nominal) 0.78 0.72 0.68 0.68
COP / EER (nominal) 3.61 / 3.8 3.61 / 3.60 3.21 / 3.30 2.81 / 3.17
SCOP / SEER (BS EN14825) 4.3 / 6.3 4.3 / 6.5 4.3/ 6.3 4.1 / 6.2
ErP ENERGY EFFICIENCY CLASS Heating/Cooling A+ / A++ A+ / A++ A+ / A++ A+ / A++
AIRFLOW (l/s) Lo-Mi-Hi 108-125-142 108-133-158 117-150-192 125-192-217
PIPE SIZE mm (in) Gas 9.52 (3/8”) 9.52 (3/8”) 12.7 (1/2”) 15.88 (5/8”)
Liquid 6.35 (1/4”) 6.35 (1/4”) 6.35 (1/4”) 6.35 (1/4”)
SOUND PRESSURE LEVEL (dBA) Lo-Mi-Hi 25-28-31 25-30-33 27-34-39 32-40-43
SOUND POWER LEVEL (dBA) 48 51 56 60
DIMENSIONS (mm) Width x Depth x Height 570(650)x570(650)x245(10) 570(650)x570(650)x245(10) 570(650)x570(650)x245(10) 570(650)x570(650)x245(10)
WEIGHT (kg) Unit / Grille 15 / 3 15 / 3 15 /3 15 /3
ELECTRICAL SUPPLY Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit Fed by Outdoor Unit
FUSE RATING (BS88) – HRC (A) 6 6 6 6
INTERCONNECTING CABLE No. Cores 4 4 4 4
GRILLE REFERENCE SLP-2FA SLP-2FA SLP-2FA SLP-2FA
WIRED REMOTE CONTROLLER REFERENCE PAR-33MAA PAR-33MAA PAR-33MAA PAR-33MAA
SUZ-KA-VA6 – OUTDOOR UNITS SUZ-KA25VA6 SUZ-KA35VA6 SUZ-KA50VA6 SUZ-KA60VA6
SOUND PRESSURE LEVEL (dBA) Heating/Cooling 48 / 47 50 / 49 52 / 52 55 / 55
SOUND POWER LEVEL (dBA) Cooling 58 62 65 65
WEIGHT (kg) 30 35 54 50
DIMENSIONS (mm) Width x Depth x Height 800 x 285 x 550 800 x 285 x 550 840 x 330 x 880 840 x 330 x 880
ELECTRICAL SUPPLY 220-240v, 50Hz 220-240v, 50Hz 220-240v, 50Hz 220-240v, 50Hz
PHASE Single Single Single Single
SYSTEM POWER
INPUT (kW)
Heating/Cooling (nominal) 0.89 / 0.68 1.11 / 0.97 1.56 / 1.39 2.28 / 1.77
Heating/Cooling (UK) 0.76 / 0.58 0.94 / 0.83 1.33 / 1.20 1.94 / 1.52
STARTING CURRENT (A) 4.2 5.1 7.0 10.1
SYSTEM RUNNING CURRENT (A) Heating/Cooling [MAX] 3.2 / 4.2 (7.2) 4.5 / 5.1 (8.7) 6.3 / 7.0  (12.3) 7.8 / 10.1 (14.4)
FUSE RATING (BS88) – HRC (A) 10 10 20 20
MAINS CABLE No. Cores 3 3 3 3
MAX PIPE LENGTH (m) 20 20 30 30
MAX HEIGHT DIFFERENCE (m) 12 12 30 30
CHARGE REFRIGERANT (kg) / CO2 EQUIVALENT (t)
R410A (GWP 2088) – 7m
0.80 / 1.67 1.15 / 2.40 1.60 / 3.34 1.60 / 3.34
MAX ADDITIONAL REFRIGERANT (kg) / CO2 EQUIVALENT (t)
R410A (GWP 2088)
0.39 / 0.81 0.39 / 0.81 0.46 / 0.96 0.46 / 0.96