Sale!

MULTI V 5 – HP 24 to 30

£12,312.00 - £15,562.50 ex. VAT

Clear

Note: All systems must be installed by Certified Installer.

Description

HP 24 26 26 28 30
Model Name Combination Unit ARUM241LTE5 ARUM260LTE5 ARUM261LTE5 ARUM280LTE5 ARUM300LTE5
Independent Units ARUM120LTE5 ARUM120LTE5 ARUM260LTE5 ARUM140LTE5 ARUM120LTE5 ARUM160LTE5 ARUM120LTE5 ARUM180LTE5 ARUM120LTE5
Capacity Cooling kW (Rated) 67,2 72,8 72,8 78,4 84,0
kW (UK) 49,70 53,8 53,85 57,95 62,10
Heating kW (Rated) 67,2 67,2 72,8 78,4 84,0
kW (UK) 67,2 67,2 72,8 78,4 84,0
Heating (Max) kW 75,6 74,3 81,9 88,2 94,5
Input Cooling kW (Rated) 15,2 20,20 16,3 18,47 18,49
kW (UK) 7,64 13,09 8,19 9,31 9,32
Heating kW (Rated) 13,7 15,99 15,0 17,13 16,97
kW (UK) 16,9 18,69 17,98 20,32 20,59
Heating (Max) kW 16,5 19,15 18,0 20,65 20,2
EER Rated 4,43 3,60 4,48 4,24 4,54
UK 6,50 4,11 6,58 6,23 6,67
ESEER Rated 7,47 6,34 7,39 6,94 7,43
UKCompleteSystem TBC 6,81 TBC TBC TBC
ESEER (SLC) Rated 8,60 7,62 8,41 8,12 8,29
COP Rated 4,91 4,20 4,86 4,58 4,95
UK 3,98 3,90 4,05 3,86 4,08
MAX 4,58 3,88 4,56 4,27 4,68
Power factor Rated 0,93 0,93 0,93 0,93 0,93
Heat Exchanger Ocean Black Fin
Compressor Type Hermetically Sealed Scroll
Piston Displacement cm3/rev 62.1 × 2 62.1 × 2 62.1 × 2 62.1 × 2 (62.1 × 2) + (43.8 × 1)
Number of Revolution rev/min 3,600 × 2 3,600 × 2 3,600 × 2 3,600 × 2 3,600 × 3
Motor Output × Number W × No. 5,300 × 2 5,300 × 2 5,300 × 2 5,300 × 2 (5,300 × 2) + (4,200 × 1)
Starting Method DC INVERTER
Oil Type FVC68D(PVE)
Fan Type Propeller fan
Motor Output × Number W (1200 × 1) + (1,200 × 1) 900 × 2 (900 × 2) + (1,200 × 1) (900 × 2) + (1,200 × 1) (900 × 2) + (1,200 × 1)
Air Flow Rate (High) m3/min (240 × 1) + (240 × 1) 320 × 1 (320 × 1) + (240 × 1) (320 × 1) + (240 × 1) (320 × 1) + (240 × 1)
Drive DC INVERTER
Discharge Side / Top TOP
Pipe Connections For Heat Recovery Liquid Pipe mm(inch) 15.88(5/8) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
Low Pressure Gas Pipe mm(inch) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8)
High Pressure Gas Pipe mm(inch) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8)
Pipe Connections For Heat Pump Liquid Pipe mm(inch) 15.88(5/8) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
Gas Pipe mm(inch) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8)
Dimensions(W × H × D) mm (930 × 1,690 × 760) × 1
+ (930 × 1,690 × 760) × 1
(1,240 × 1,690 × 760) ×1 (1,240 × 1,690 × 760) × 1
+ (930 × 1,690 × 760) × 1
(1,240 × 1,690 × 760) × 1
+ (930 × 1,690 × 760) × 1
(1,240 × 1,690 × 760) × 1
+ (930 × 1,690 × 760) × 1
Net Weight kg (215 × 1) + (215 × 1) 310 × 1 (237 × 1) + (215 × 1) (237 × 1) + (215 × 1) (300 × 1) + (215 × 1)
Sound Pressure Level Cooling dB(A) 62,0 65,0 62,5 62,8 63,1
Heating dB(A) 63,0 67,0 63,5 63,8 64,1
Sound Power
Level
Cooling dB(A) 82,0 88,0 83,8 84,5 86,0
Heating dB(A) 83,0 90,0 85,5 86,2 87,0
Communication Cable No.×mm2(VCTF-SB) 2C × 1.0 ~ 1.5
Refrigerant Refrigerant name R410A
Precharged Amount kg 19,0 17,0 23,0 23,0 25,5
GWP 2,087.5
TCO2eq 39,7 35,5 48,0 48,0 53,2
Control Electronic Expansion Valve
Maximum Starting Current A 11,8 11,8 11,8 11,8 16,1
Maximum Running Current A 50,9 49,1 50,9 50,9 68,2
Maximum Fuse Amperes A 32 + 32 63 32 + 32 32 + 32 50 + 32
Power Supply Ø , V, Hz 380~415, 3, 50
Number of maximum connectable indoor units 39(48) 42(64) 42(52) 45(56) 49(60)

Additional information

MULTI V 5 - HP 24 to 30

ARUM241LTE5, ARUM260LTE5, ARUM261LTE5, ARUM280LTE5, ARUM300LTE5

Reviews

There are no reviews yet.

Be the first to review “MULTI V 5 – HP 24 to 30”

Downloads

No files uploaded.