Sale!

MULTI V S HEAT RECOVERY – SINGLE PHASE

Compare

From: £2,965.20 ex. VAT

Clear

Description

SINGLE PHASE – 3 PIPE – HEAT RECOVERY 6
OUTDOOR UNIT   ARUB060GSS4
Capacity 1) (Rated) Cooling kW 15,5
Heating kW 18,0
Cooling kWa) 11,5
Heating kWa) 18,0
Input (Rated) 1) Cooling  kW 3,97
Heating kW 4,10
Cooling kWa) 2,00
Heating kWa) 5,01
EER Rated 3,90
EER UK 5,75
COP Rated 4,39
COP UK 3,59
Power Factor 7) Rated                      – 0,93
Casing Colour Warm Gray
Heat Exchanger OCEAN BLACK FIN
Compressor Type Hermetically Sealed Scroll
Piston Displacement  cm3/rev 43,8
Number of                rev/min
Revolution
3 600
Motor Output W 4 200
Starting Method DC Inverter Starting
Oil Type FVC68D(PVE)
Fan Type Axial Flow Fan
Motor Output x Number W 124 x 2
Air Flow Rate (High)  m3/min 110
Drive DC INVERTER
Discharge  Side / Top Side
Pipe Connections Liquid  mm (inch) Ø 9.52 (3/8)
Gas High Pressure mm (inch) Ø 15.88 (5/8)
Gas Low Pressure mm (inch) Ø 19.05 (3/4)
Dimensions W x H x D mm 950 × 1,380 × 330
Net Weight kg 118
Sound Pressure Level Cooling dB(A) 56
Heating dB(A) 58
Sound Power Level Cooling dB(A) 69
Heating dB(A) 71
Protection Devices High pressure protection High pressure sensor / High pressure switch
Compressor / Fan Over-heat protection / Fan driver overload protector
Inverter Over-heat protection / Over-current protection
Communication Cable 2C x 1.0 ~ 1.5
Refrigerant Type R410A
Precharged Amount   kg 3,5
GWP 2087,5
t-CO2 eq 7,3
Control Electronic Expansion Valve
Refrigerant Oil Type FVC68D(PVE)
Charge cc
Power Supply V, Ø, Hz 220 – 240, 1, 50
Maximum Starting Current A 4,3
Minimum CircuitAmperes A 36
Maximum Fuse Amperes A 40
Number of Maxmum Connectable Indoor Units 3) 13