Indoor unit   FDUM40VF FDUM50VF FDUM60VF FDUM71VF1 FDUM100VF2 FDUM125VF FDUM140VF
Outdoor unit   SRC40ZSX-S SRC50ZSX-S SRC60ZSX-S FDC71VNX FDC100VNX FDC125VNX FDC140VNX
Power source 1 Phase 220-240V, 50Hz / 220V, 60Hz
Nominal cooling capacity (Min~Max) kW 4.0(1.1~4.7 ) 5.0(1.1~5.6 ) 5.6(1.1~6.3) 7.1(3.2~8.0) 10.0(4.0~11.2) 12.5(5.0~14.0) 14.0(5.0~16.0)
Nominal heating capacity (Min~Max) kW 4.5(0.6~5.4 ) 5.4(0.6~6.3 ) 6.7(0.6~7.1) 8.0(3.6~9.0) 11.2(4.0~12.5) 14.0(4.0~17.0) 16.0(4.0~18.0)
Power consumption Cooling/Heating kW 0.952 / 1.07 1.38 / 1.45 1.54 / 1.75 2.03 / 1.99 2.68 / 3.02 3.49 / 3.77 4.28 / 4.42
EER/COP Cooling/Heating 4.20 / 4.21 3.62 / 3.72 3.64 / 3.83 3.50 / 4.02 3.73 / 3.71 3.58 / 3.71 3.27 / 3.62
Inrush current A 5 5 5 5 5 5 5
Max. current 12 15 15 17 24 26 26
Sound power level*1 Indoor Cooling/Heating dB(A) 60 / 60 60 / 60 60 / 60 65 / 65 65 / 65 67 / 67 70 / 70
Outdoor Cooling/Heating 63 / 63 63 / 63 65 / 64 66 / 66 70 / 70 70 / 70 72 / 72
Sound pressure level*1    1 Indoor Cooling (Hi/Me/Lo) 32 / 29 / 26 32 / 29 / 26 31 / 28 / 25 33 / 29 / 25 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Heating (Hi/Me/Lo) 32 / 29 / 26 32 / 29 / 26 31 / 28 / 25 33 / 29 / 25 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Outdoor Cooling/Heating 50 / 49 50 / 49 52 / 52 51 / 48 48 / 50 48 / 50 49 / 52
Air flow    1
Indoor Cooling (Hi/Me/Lo) m3/min 10 / 9 / 8 10 / 9 / 8 15 / 13 / 10 19 / 15 / 10 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Heating (Hi/Me/Lo) 10 / 9 / 8 10 / 9 / 8 15 / 13 / 10 19 / 15 / 10 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Outdoor Cooling/Heating 36 / 33 40 / 33 41.5 / 39 60 / 50 100 / 100 100 / 100 100 / 100
External static pressure*3 Pa Standard:35  Max:100 Standard:60  Max:100
Exterior dimensions Indoor HeightxWidthxDepth mm 280x750x635 280x950x635 280×1,370×740
Outdoor 640×800(+71)x290 750×880(+88)x340 1,300x970x370
Net weight Indoor kg 29 34 54
Outdoor 45 60 105
Ref.piping size Liquid/Gas ømm 6.35(1/4″) / 12.7(1/2″) 9.52(3/8″) / 15.88(5/8″)
Refrigerant line (one way) length m Max.30 Max.50 Max.100
Vertical height differences Outdoor is higher/lower m Max.20 / Max.20 Max.30 / Max.15
Outdoor operating temperature range Cooling °C -15~46*4 -15~43*4
Heating -20~24 -20~20
Air filter Filter kit : UM-FL1EF / UM-FL2EF / UM-FL3EF (option)
Remote control (option) wired:RC-EX3, RC-E5, RCH-E3  wireless:RCN-KIT4-E2