Sale!

FDUM Hyper Inverter Ducted 1Phase

Compare

From: £878.25 - £2,176.50 ex. VAT

Clear

Description

Indoor unit FDUM40VFFDUM50VFFDUM60VFFDUM71VF1FDUM100VF2FDUM125VFFDUM140VF
Outdoor unit SRC40ZSX-SSRC50ZSX-SSRC60ZSX-SFDC71VNXFDC100VNXFDC125VNXFDC140VNX
Power source1 Phase 220-240V, 50Hz / 220V, 60Hz
Nominal cooling capacity (Min~Max)kW4.0(1.1~4.7 )5.0(1.1~5.6 )5.6(1.1~6.3)7.1(3.2~8.0)10.0(4.0~11.2)12.5(5.0~14.0)14.0(5.0~16.0)
Nominal heating capacity (Min~Max)kW4.5(0.6~5.4 )5.4(0.6~6.3 )6.7(0.6~7.1)8.0(3.6~9.0)11.2(4.0~12.5)14.0(4.0~17.0)16.0(4.0~18.0)
Power consumptionCooling/HeatingkW0.952 / 1.071.38 / 1.451.54 / 1.752.03 / 1.992.68 / 3.023.49 / 3.774.28 / 4.42
EER/COPCooling/Heating4.20 / 4.213.62 / 3.723.64 / 3.833.50 / 4.023.73 / 3.713.58 / 3.713.27 / 3.62
Inrush currentA5555555
Max. current12151517242626
Sound power level*1IndoorCooling/HeatingdB(A)60 / 6060 / 6060 / 6065 / 6565 / 6567 / 6770 / 70
OutdoorCooling/Heating63 / 6363 / 6365 / 6466 / 6670 / 7070 / 7072 / 72
Sound pressure level*1    1IndoorCooling (Hi/Me/Lo)32 / 29 / 2632 / 29 / 2631 / 28 / 2533 / 29 / 2538 / 36 / 3040 / 34 / 2940 / 35 / 30
Heating (Hi/Me/Lo)32 / 29 / 2632 / 29 / 2631 / 28 / 2533 / 29 / 2538 / 36 / 3040 / 34 / 2940 / 35 / 30
OutdoorCooling/Heating50 / 4950 / 4952 / 5251 / 4848 / 5048 / 5049 / 52
Air flow    1
IndoorCooling (Hi/Me/Lo)m3/min10 / 9 / 810 / 9 / 815 / 13 / 1019 / 15 / 1028 / 25 / 1932 / 26 / 2035 / 28 / 22
Heating (Hi/Me/Lo)10 / 9 / 810 / 9 / 815 / 13 / 1019 / 15 / 1028 / 25 / 1932 / 26 / 2035 / 28 / 22
OutdoorCooling/Heating36 / 3340 / 3341.5 / 3960 / 50100 / 100100 / 100100 / 100
External static pressure*3PaStandard:35  Max:100Standard:60  Max:100
Exterior dimensionsIndoorHeightxWidthxDepthmm280x750x635280x950x635280×1,370×740
Outdoor640×800(+71)x290750×880(+88)x3401,300x970x370
Net weightIndoorkg293454
Outdoor4560105
Ref.piping sizeLiquid/Gasømm6.35(1/4″) / 12.7(1/2″)9.52(3/8″) / 15.88(5/8″)
Refrigerant line (one way) lengthmMax.30Max.50Max.100
Vertical height differencesOutdoor is higher/lowermMax.20 / Max.20Max.30 / Max.15
Outdoor operating temperature rangeCooling°C-15~46*4-15~43*4
Heating-20~24-20~20
Air filterFilter kit : UM-FL1EF / UM-FL2EF / UM-FL3EF (option)
Remote control (option)wired:RC-EX3, RC-E5, RCH-E3  wireless:RCN-KIT4-E2

Reviews

There are no reviews yet.

Be the first to review “FDUM Hyper Inverter Ducted 1Phase”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.