Sale!

FDU-VF Hyper Inverter Ducted 1Phase

Compare

From: £1,288.50 - £2,118.00 ex. VAT

Clear

Description

Indoor unit FDU71VF1FDU100VF2FDU125VFFDU140VF
Outdoor unit FDC71VNXFDC100VNXFDC125VNXFDC140VNX
Power source1 Phase 220-240V, 50Hz / 220V, 60Hz
Nominal cooling capacity (Min~Max)kW7.1 ( 3.2 ~ 8.0 )10.0 ( 4.0 ~ 11.2 )12.5 ( 5.0 ~ 14.0 )14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max)kW8.0 ( 3.6 ~ 9.0 )11.2 ( 4.0 ~ 12.5 )14.0 ( 4.0 ~ 17.0 )16.0 ( 4.0 ~ 18.0 )
Power consumptionCooling/HeatingkW2.05 / 2.012.68 / 3.023.49 / 3.774.28 / 4.42
EER/COPCooling/Heating3.46 / 3.983.73 / 3.713.58 / 3.713.27 / 3.62
Inrush currentA5555
Max. current17252930
Sound power level*1IndoorCooling/HeatingdB(A)65 / 6565 / 6567 / 6770 / 70
OutdoorCooling/Heating66 / 6670 / 7070 / 7072 / 72
Sound pressure level*1    1IndoorCooling (Hi/Me/Lo)33 / 29 / 2538 / 36 / 3040 / 34 / 2940 / 35 / 30
Heating (Hi/Me/Lo)33 / 29 / 2538 / 36 / 3040 / 34 / 2940 / 35 / 30
OutdoorCooling/Heating51 / 4848 / 5048 / 5049 / 52
Air flow    1
IndoorCooling (Hi/Me/Lo)m3/min19 / 15 / 1028 / 25 / 1932 / 26 / 2035 / 28 / 22
Heating (Hi/Me/Lo)19 / 15 / 1028 / 25 / 1932 / 26 / 2035 / 28 / 22
OutdoorCooling/Heating60 / 50100 / 100100 / 100100 / 100
External static pressure*2PaStandard:35  Max:200Standard:60  Max:200
Exterior dimensionsIndoorHeightxWidthxDepthmm280 x 950 x 635280 x 1,370 x 740
Outdoor750 x 880(+88) x 3401,300 x 970 x 370
Net weightIndoorkg3454
Outdoor60105
Ref.piping sizeLiquid/Gasømm9.52(3/8″) / 15.88(5/8″)
Refrigerant line (one way) lengthmMax.50Max.100
Vertical height differencesOutdoor is higher/lowermMax.30 / Max.15
Outdoor operating temperature rangeCooling°C-15~43*3
Heating-20~20
Air filterProcure locally
Remote control (option)wired:RC-EX3, RC-E5, RCH-E3  wireless:RCN-KIT4-E2

Reviews

There are no reviews yet.

Be the first to review “FDU-VF Hyper Inverter Ducted 1Phase”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.