Flexi-Floor/Ceiling Mounted Split Systems R410A

From: £1,137.00£1,490.00

SKU: N/A Category: Tags: , , , , ,

Note: All systems must be installed by Certified Installer.

Description

Indoor Units FLXS25B FLXS35B9 FLXS50B
Capacity UK Total Cooling kW 2.44 3.34 4.82
UK Sensible Cooling kW 1.65 2.14 3.16
Nominal Cooling kW 2.5 3.5 4.9
Nominal Heating kW 3.4 4.0 6.1
Seasonal Efficiency (EN14825) COOLING Energy Label A B A
Pdesign kW 2.5 3.5 4.9
SEER 5.19 4.87 5.25
Annual Energy Consumption kWh 169 252 326
Seasonal Efficiency (EN14825) HEATING Energy Label A A A
Pdesign kW 2.5 2.9 4.2
SCOP 3.80 3.80 3.80
Annual Energy Consumption kWh 921 1068 1546
Nominal Efficiency EER / COP 3.85 / 3.54 2.88 / 3.57 2.85 / 3.35
Air Flow Rate (Cooling) High / Nom / Low / Silent m3/sec 0.127 / 0.127 / 0.100 / 0.087 0.143 / 0.127 / 0.110 / 0.093 0.190 / 0.190 / 0.142 / 0.125
Dimensions Height mm 490 490 490
Width mm 1050 1050 1050
Depth mm 200 200 200
Weight kg 16 16 17
Sound Pressure (Cooling) High / Nom / Low / Silent dBA 37 / 34 / 31 / 28 38 / 35 / 32 / 29 47 / 43 / 39 / 36
Sound Pressure (Heating) High / Nom / Low / Silent dBA 37 / 34 / 31 / 28 46 / – / 33 / 30 46 / – / 35 / 33
Sound Power (Cooling) dBA 51 53 60
Outdoor Units RXS25L3 RXS35L3 RXS50L
Dimensions Height x Width x Depth mm 550 x 765 x 285 550 x 765 x 285 735 x 825 x 300
Weight kg 34 34 47
Electrical Details Power Supply 1ph
Running Current A 3.60 5.10 7.60
Starting Current A 3.3 4.3 6.8
Max Fuse Size A 10 10 20
Interconnection Wiring Core / Cable size 3+E / 1.5 3+E / 1.5
Piping Connections Liquid / Gas inches (mm) 1/4 (6.4) / 3/8 (9.5) 1/4 (6.4) / 1/2 (12.7)
Pipework Maximum Length m 20 20 30
Maximum Vertical Rise m 15 15 20
Precharged to m 10 10 10
Additional Charge g/m 20
Holding Charge kg 1.00 1.20 1.70
Sound Pressure (Cooling) High / Silent Operation dBA 46 / 43 48 / 44 48 / 44
Sound Pressure (Heating) High / Silent Operation dBA 48 / 45 48 / 45 48 / –
Sound Power (Cooling) dBA 59 61 62
Operating Range (Cooling) Min / Max °CDB -10 / 46 -10 / 46 -10 / 46
Operating Range (Heating) Min / Max °CWB -15 / 18 -15 / 18 -15 / 18
Air Flow Rate (Cooling) High / Super low m3/sec 0.558 / 0.502 0.600 / 0.502 0.848 / 0.815