Description
Kit | KIT-71PK2E8D | KIT-100PK2E8D | ||
Remote controller | CZ-RTC5B | CZ-RTC5B | ||
Cooling capacity | Nominal (Min – Max) | kW | 7.1 (3.2 – 8.0) | 9.5 (3.3 – 10.5) |
UK Cooling capacity | Total / Sensible | kW | 7.9 / 5.9 | 9.6 / 6.5 |
EER | Nominal (Min – Max) | W/W | 3.40 (5.71 – 3.02) A | 3.25 (3.93 – 3.09) A |
SEER | W/W | 6.50 A++ | 6.10 A+ | |
Pdesign | kW | 7.1 | 9.5 | |
Input power cooling | Nominal (Min – Max) | kW | 2.09 (0.56 – 2.65) | 2.92 (0.84 – 3.40) |
Annual energy consumption (ErP) | kWh/a | 382 | 545 | |
Heating capacity | Nominal (Min – Max) | kW | 8.0 (2.8 – 9.0) | 9.5 (4.1 – 11.5) |
UK Heating capacity | kW | 8.1 | 11.5 | |
Heating capacity at -7°C / -15°C | kW | — /— | — /— | |
COP | Nominal (Min – Max) | W/W | 4.00 (5.60 – 3.10) A | 3.97 (4.56 – 3.43) A |
SCOP | W/W | 4.10 A+ | 4.00 A+ | |
Pdesign at -10°C | kW | 7.10 | 9.50 | |
Input power heating | Nominal (Min – Max) | kW | 2.00 (0.50 – 2.90) | 2.39 (0.90 – 3.35) |
Annual energy consumption (ErP) | kWh/a | 2424 | 3325 | |
Indoor unit | S-71PK2E5B | S-100PK2E5B | ||
Air volume | Hi / Med / Lo | m³/min | 20.00 / 17.50 / 14.50 | 22.00 / 18.50 / 15.00 |
Sound pressure | Hi / Med / Lo | dB(A) | 47 / 44 / 40 | 49 / 45 / 41 |
Dimension | H x W x D | mm | 302 x 1120 x 236 | 302 x 1120 x 236 |
Net weight | kg | 14 | 14 | |
Outdoor unit | U-71PE1E8A | U-100PE1E8A | ||
Power source | V | 380 / 400 / 415 | 380 / 400 / 415 | |
Recommended fuse | A | 16 | 16 | |
Connection | mm² | 2.50 | 2.50 | |
Current | Cool | A | 3.25 / 3.10 / 3.00 | 4.60 / 4.35 / 4.30 |
Heat | A | 3.05 / 3.00 / 2.85 | 3.70 / 3.55 / 3.45 | |
Air volume | Cool / Heat | m³/min | 60 / 60 | 110 / 95 |
Sound pressure | Cool / Heat (Hi) | dB(A) | 48 / 50 | 52 / 52 |
Dimension | H x W x D | mm | 996 x 940 x 340 | 1416 x 940 x 340 |
Net weight | kg | 71 | 98 | |
Piping connections | Liquid pipe | Inch (mm) | 3/8 (9.52) | 3/8 (9.52) |
Gas pipe | Inch (mm) | 5/8 (15.88) | 5/8 (15.88) | |
Pipe length range | m | 5 – 50 | 5 – 75 | |
Elevation difference (in/out) | m | 30 | 30 | |
Pipe length for additional gas | m | 30 | 30 | |
Additional gas amount | g/m | 50 | 50 | |
Refrigerant (R410A) | kg / TCO2 Eq. | 2.35 / 4.9068 | 3.40 / 7.0992 | |
Operating range | Cool Min ~ Max | °C | -15 ~ +46 | -15 ~ +46 |
Heat Min ~ Max | °C | -20 ~ +24 | -20 ~ +24 |
Reviews