Indoor UnitMML-AP0124BH1-EAP0184BH1-EAP0244BH1-E
Outdoor UnitRAV-SP404ATP-ESP564ATP-ESP804ATP-E
NominalCooling CapacitykW3.65.07.1
Heating CapacitykW4.05.68.0
EER/COPW/W2.94/0.053.50/0.093.76/0.09
UKCooling Total/SensiblekW3.40/3.005.1/3.96.4/5.0
HeatingkW2.614.305.40
Cooling EN14825Range Min. – Max.kW1.5 – 4.01.2 – 5.61.9 – 8.0
Power InputkW1.221.431.89
PdesignkW
SEER/Energy Efficiency Class
Seasonal Energy ConsumptionkWh/a
Heating EN14825Range Min. – Max.kW1.5 – 5.00.9 – 7.41.3 – 10.6
Power InputkW0.801.341.95
PdesignkW
SCOP/Energy Efficiency Class
Seasonal Energy ConsumptionkWh/a
Indoor DataMML-AP0124BH1-EAP0184BH1-EAP0244BH1-E
Air FlowHigh – Medium – Lowl/s133 – 117 – 83200 – 167 – 133267 – 217 – 183
High – Medium – Lowm3/h460 – 400 – 300740 – 600 – 490950 – 790 – 640
External Static PressurePa555
SoundPressure High – Medium – LowdB(A)36 – 34 – 3236 – 34 – 3242 – 37 – 33
Power High – Medium – LowdB(A)51 – 49 – 4751 – 49 – 4757 – 52 – 48
UnitHeight x Width x Depthmm600 x 745 x 220600 x 1045 x 220600 x 1045 x 220
Weightkg212929
Pipe ConnectionFlare Connections (gas – liquid)inch3/8 – 1/41/2 – 1/45/8 – 3/8
Drain Pipe Connectionmm20 male screw20 male screw20 male screw
Remote ControllerRBC-AMT32ERBC-AMT32ERBC-AMT32E
Outdoor DataRAV-SP404ATP-ESP564ATP-ESP804ATP-E
Operating RangeCooling/Heating°C43 to -15/15 to -1543 to -15/15 to -2043 to -15/15 to -20
Air FlowHighm3/h – l/s2400 – 6672400 – 6673000 – 833
SoundPressure High Cooling/HeatingdB(A)45/4747/4848/49
Power High Cooling/HeatingdB(A)62/6463/6464/65
UnitHeight x Width x Depthmm550 x 780 x 290550 x 780 x 290890 x 900 x 320
Weightkg404466
Pipe ConnectionFlare Connections (gas – liquid)inch1/2 – 1/41/2 – 1/45/8 – 3/8
Min.-Max. Lengthm5-305-505-50
Maximum Height Differencem±30±30±30
Drain Port Connectionmm161616
Refrigerant R410ABase Charge/Chargeless Lengthkg/m1.0/201.4/202.1/30
Additional Charge Liquid Sideg/m202040
Run CurrentMaximumA5.196.969.42
Power CableOutdoor to Indoor3 core + earth3 core + earth3 core + earth
Power SupplySuggested Fuse SizeV/ph/Hz-A220-240/1/50-10220-240/1/50-16220-240/1/50-16