Indoor UnitRAV-GM561UT-EGM801UT-EGM1101UT-EGM1401UT-E
Outdoor UnitRAV-GP561ATP-EGP801AT-EGP1101AT-EGP1401AT-E
NominalCooling CapacitykW5.07.110.012.5
Heating CapacitykW5.68.011.214.0
EER/COPW/W3.29/3.485.18/5.525.26/5.144.30/4.61
UKCooling Total/SensiblekW4.8/4.07.4/6.29.5/8.011.9/9.4
HeatingkW3.555.258.009.76
Cooling EN14825Range Min. – Max.kW1.2 – 5.61.9 – 8.03.1 – 12.03.1 – 14.0
Power InputkW1.521.371.902.91
PdesignkW5.007.1010.0012.50
SEER/Energy Efficiency Class (or ηsc %)8.07 /A++9.40/A+++8.80/A+++8.30/329
Seasonal Energy ConsumptionkWh/a217264398903
Heating EN14825Range Min. – Max.kW0.9 – 7.41.3 – 11.32.6 – 13.02.6 – 16.5
Power InputkW1.611.452.183.04
PdesignkW3.805.109.209.60
SCOP/Energy Efficiency Class (or ηsc(A) %)5.01/A++5.51/A+++5.00/A++4.97/195.8
Seasonal Energy ConsumptionkWh/a1061129425732702
Indoor DataRAV-GM561UT-EGM801UT-EGM1101UT-EGM1401UT-E
Air FlowHigh – Medium – Lowl/s292 – 250 – 208533 – 36 – 225625 – 458 – 292625 – 475 – 325
High – Medium – Lowm3/h1050 – 900 – 7501920 – 129 – 8102250 – 1650 – 10502250 – 1710 – 1170
SoundPressure High – Medium – LowdB(A)32 – 29 – 2642 – 35 – 2748 – 40 – 3148 – 41 – 33
Power High – Medium – LowdB(A)48 – 45 – 4356 – 49 – 4361 – 54 – 4661 – 55 – 48
UnitHeight x Width x Depthmm256 x 840 x 840319 x 840 x 840319 x 840 x 840319 x 840 x 840
Weightkg20252525
PanelHeight x Width x Depthmm30 x 950 x 95030 x 950 x 95030 x 950 x 95030 x 950 x 950
Weight RBC-U41PG(W)-Ekg5555
Pipe ConnectionFlare Connections (gas – liquid)inch1/2 – 1/45/8 – 3/85/8 – 3/85/8 – 3/8
Drain Pipe Connection OD/IDmmVP32/25VP32/25VP32/25VP32/25
Remote ControllerRBC-AMT32ERBC-AMT32ERBC-AMT32ERBC-AMT32E
Outdoor DataRAV-GP561ATP-EGP801AT-EGP1101AT-EGP1401AT-E
Operating RangeCooling/Heating°C-15 to 52/-27 to 15-15 to 52/-27 to 15-15 to 52/-27 to 15-15 to 52/-27 to 15
Air FlowHighm3/h – l/s2250 – 6253180 – 8836960 – 19346960 – 1934
SoundPressure High Cooling/HeatingdB(A)46/4846/4849/5050/51
Power High Cooling/HeatingdB(A)63/6563/6566/6767/68
UnitHeight x Width x Depthmm630 x 799 x 2991050 x 1010 x 3701550 x 1010 x 3701550 x 1010 x 370
Weightkg4574104104
Pipe ConnectionFlare Connections (gas – liquid)inch1/2 – 1/45/8 – 3/85/8 – 3/85/8 – 3/8
Min.-Max. Lengthm3-503-503-753-75
Maximum Height Differencem±30±30±30±30
Drain Port Connectionmm16161616
RefrigerantGas – Base Charge/Chargeless Lengthkg/mR32 – 1.35/20R32 – 1.9/30R32 – 3.1/30R32 – 3.1/30
Additional Charge Liquid Sideg/m20353535
Run CurrentMaximumA7.667.0110.4314.55
Power CableOutdoor to Indoor3 core + earth3 core + earth3 core + earth3 core + earth
Power SupplySuggested Fuse SizeV/ph/Hz-A220-240/1/50-16220-240/1/50-16220-240/1/50-20220-240/1/50-25