PEA-RP – INDOORPEA-RP200WKAPEA-RP250WKA
CAPACITY (kW)Heating (nominal)22.4 (9.5-25.0)27.0 (12.5-31.0)
Cooling (nominal)19.0 (9.0-22.4)22.0 (11.2-27.0)
Heating (UK)19.05 (8.1-21.25)22.95 (10.65-26.35)
Cooling (UK)17.5 (8.3-20.6)20.25 (10.3-24.85)
SHF (nominal)0.810.86
COP / EER (nominal)3.30 / 3.023.10 / 2.70
SCOP (ƞsh) / SEER (ƞsc) (BS EN14825)3.36 (134.4%) / 4.86 (194.5%)3.35 (133.9%) / 4.59 (183.7%)
AIRFLOW (l/s)                                                Lo-Mi-Hi833-1017-1200967-1183-1400
PIPE SIZE mm (in)Gas28.58 (1 1/8”)28.58 (1 1/8”)
Liquid9.52 (3/8”)12.7 (1/2”)
EXTERNAL STATIC PRESSURE (Pa)60 / 75 / 100 / 15060 / 75 / 100 / 150
SOUND PRESSURE LEVEL (dBA) (60Pa)Lo-Mi-Hi38-41-4440-43-46
SOUND POWER LEVEL (dBA) (60Pa)Lo-Mi-Hi65-66-6770-71-72
DIMENSIONS (mm)Width x Depth x Height1370 x 1120 x 4701370 x 1120 x 470
WEIGHT (kg)108108
ELECTRICAL SUPPLY220-240v, 50Hz220-240v, 50Hz
PHASESingleSingle
POWER INPUT (kW)Nominal / UK0.66 / 0.590.80 / 0.71
STARTING CURRENT (A)7.17.1
RUNNING CURRENT (A)   [MAX]3.57 [4.3]4.34 [5.5]
FUSE RATING (BS88) – HRC (A)1616
MAINS CABLE No. Cores33
INTERCONNECTING CABLE No. Cores33
WIRED REMOTE CONTROLLER REFERENCEPAR-33MAAPAR-33MAA
PUHZ-P – OUTDOOR UNITSPUHZ-P200YKA3PUHZ-P250YKA3
SOUND PRESSURE LEVEL (dBA)Heating/Cooling60 / 5862 / 59
WEIGHT (kg)127135
DIMENSIONS (mm)Width x Depth x Height1050 x 330+40 x 13381050 x 330+40 x 1338
ELECTRICAL SUPPLY380-415v, 50Hz380-415v, 50Hz
PHASEThreeThree
SYSTEM POWERHeating/Cooling (nominal)6.78 / 6.298.70 / 8.14
INPUT (kW)Heating/Cooling (UK)6.10 / 5.227.83 / 6.75
STARTING CURRENT (A)55
RUNNING CURRENT (A)Heating/Cooling [MAX]11.45 / 11.04 [19]14.04 / 13.04 [21]
FUSE RATING (BS88) – HRC (A)3232
MAINS CABLE No. Cores55
MAX PIPE LENGTH (m)7070
MAX HEIGHT DIFFERENCE (m)3030
CHARGE REFRIGERANT (kg) / CO2 EQUIVALENT (t)
R410A (GWP 2088) – 30m
6.50 / 13.577.70 / 16.08
MAX ADDITIONAL REFRIGERANT (kg) / CO2 EQUIVALENT (t)
R410A (GWP 2088)
3.60 / 7.52 (70m)4.80 / 10.02 (70m)

Additional information

PEA-RP R410A Large Capacity Ceiling Concealed Ducted System Standard Inverter Heat Pump (Three Phase)

,

Reviews

There are no reviews yet.

Be the first to review “PEA-RP R410A Large Capacity Ceiling Concealed Ducted System Standard Inverter Heat Pump (Three Phase)”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.