Sale!

PEA-RP R410A Large Capacity Ceiling Concealed Ducted System Standard Inverter Heat Pump (Three Phase)

Compare

From: £4,730.40 - £5,160.60 ex. VAT

Clear

Description

PEA-RP – INDOOR PEA-RP200WKA PEA-RP250WKA
CAPACITY (kW) Heating (nominal) 22.4 (9.5-25.0) 27.0 (12.5-31.0)
Cooling (nominal) 19.0 (9.0-22.4) 22.0 (11.2-27.0)
Heating (UK) 19.05 (8.1-21.25) 22.95 (10.65-26.35)
Cooling (UK) 17.5 (8.3-20.6) 20.25 (10.3-24.85)
SHF (nominal) 0.81 0.86
COP / EER (nominal) 3.30 / 3.02 3.10 / 2.70
SCOP (ƞsh) / SEER (ƞsc) (BS EN14825) 3.36 (134.4%) / 4.86 (194.5%) 3.35 (133.9%) / 4.59 (183.7%)
AIRFLOW (l/s)                                                Lo-Mi-Hi 833-1017-1200 967-1183-1400
PIPE SIZE mm (in) Gas 28.58 (1 1/8”) 28.58 (1 1/8”)
Liquid 9.52 (3/8”) 12.7 (1/2”)
EXTERNAL STATIC PRESSURE (Pa) 60 / 75 / 100 / 150 60 / 75 / 100 / 150
SOUND PRESSURE LEVEL (dBA) (60Pa) Lo-Mi-Hi 38-41-44 40-43-46
SOUND POWER LEVEL (dBA) (60Pa) Lo-Mi-Hi 65-66-67 70-71-72
DIMENSIONS (mm) Width x Depth x Height 1370 x 1120 x 470 1370 x 1120 x 470
WEIGHT (kg) 108 108
ELECTRICAL SUPPLY 220-240v, 50Hz 220-240v, 50Hz
PHASE Single Single
POWER INPUT (kW) Nominal / UK 0.66 / 0.59 0.80 / 0.71
STARTING CURRENT (A) 7.1 7.1
RUNNING CURRENT (A)   [MAX] 3.57 [4.3] 4.34 [5.5]
FUSE RATING (BS88) – HRC (A) 16 16
MAINS CABLE No. Cores 3 3
INTERCONNECTING CABLE No. Cores 3 3
WIRED REMOTE CONTROLLER REFERENCE PAR-33MAA PAR-33MAA
PUHZ-P – OUTDOOR UNITS PUHZ-P200YKA3 PUHZ-P250YKA3
SOUND PRESSURE LEVEL (dBA) Heating/Cooling 60 / 58 62 / 59
WEIGHT (kg) 127 135
DIMENSIONS (mm) Width x Depth x Height 1050 x 330+40 x 1338 1050 x 330+40 x 1338
ELECTRICAL SUPPLY 380-415v, 50Hz 380-415v, 50Hz
PHASE Three Three
SYSTEM POWER Heating/Cooling (nominal) 6.78 / 6.29 8.70 / 8.14
INPUT (kW) Heating/Cooling (UK) 6.10 / 5.22 7.83 / 6.75
STARTING CURRENT (A) 5 5
RUNNING CURRENT (A) Heating/Cooling [MAX] 11.45 / 11.04 [19] 14.04 / 13.04 [21]
FUSE RATING (BS88) – HRC (A) 32 32
MAINS CABLE No. Cores 5 5
MAX PIPE LENGTH (m) 70 70
MAX HEIGHT DIFFERENCE (m) 30 30
CHARGE REFRIGERANT (kg) / CO2 EQUIVALENT (t)
R410A (GWP 2088) – 30m
6.50 / 13.57 7.70 / 16.08
MAX ADDITIONAL REFRIGERANT (kg) / CO2 EQUIVALENT (t)
R410A (GWP 2088)
3.60 / 7.52 (70m) 4.80 / 10.02 (70m)

Additional information

PEA-RP R410A Large Capacity Ceiling Concealed Ducted System Standard Inverter Heat Pump (Three Phase)

,

Reviews

There are no reviews yet.

Be the first to review “PEA-RP R410A Large Capacity Ceiling Concealed Ducted System Standard Inverter Heat Pump (Three Phase)”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.