PACi STANDARD 3Phase • S-100PK2E5B

  • Full Systems (Indoor + Outdoor Units + Remote Controller)

From: £2,209.00 ex. VAT


Note: All systems must be installed by Certified Installer.

Description

Kit KIT-100PKY2E8D
Remote controller CZ-RTC5B
Cooling capacity Nominal (Min – Max) kW 9.0 (2.7 – 9.7)
UK Cooling capacity Total / Sensible kW 8.9 / 6.0
EER Nominal (Min – Max) W/W 2.67 (5.09 – 2.55) D
SEER W/W 5.80 A+
Pdesign kW 9.0
Input power cooling Nominal (Min – Max) kW 3.37 (0.53 – 3.80)
Annual energy consumption (ErP) kWh/a 543
Heating capacity Nominal (Min – Max) kW 9.0 (2.1 – 10.5)
UK Heating capacity kW 9.8
Heating capacity at -7°C / -15°C kW 9.97 / 8.43
COP Nominal (Min – Max) W/W 3.78 (5.12 – 3.50) A
SCOP W/W 3.90 A
Pdesign at -10°C kW 9.00
Input power heating Nominal (Min – Max) kW 2.38 (0.41 – 3.00)
Annual energy consumption (ErP) kWh/a 3231
Indoor unit   S-100PK2E5B
Air volume Hi / Med / Lo m³/min 22.00 / 18.50 / 15.00
Sound pressure Hi / Med / Lo dB(A) 49 / 45 / 41
Dimension H x W x D mm 302 x 1120 x 236
Net weight kg 14
Outdoor unit   U-100PEY1E8
Power source V 380 / 400 / 415
Recommended fuse A 16
Connection mm² 2.5
Current Cool A 5.40 / 5.10 / 4.95
Heat A 3.75 / 3.55 / 3.45
Air volume Cool / Heat m³/min 76 / 67
Sound pressure Cool / Heat (Hi) dB(A) 54 / 54
Dimension H x W x D mm 996 x 940 x 340
Net weight kg 73
Piping connections Liquid pipe Inch (mm) 3/8 (9.52)
Gas pipe Inch (mm) 5/8 (15.88)
Pipe length range m 5 – 50
Elevation difference (in/out) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 50
Refrigerant (R410A) kg / TCO2 Eq. 2.60 / 5.4288
Operating range Cool Min ~ Max °C -10 / +43
Heat Min ~ Max °C -15 / +24

Additional information

PACi STANDARD Wall Mounted Inverter+ 3 Phase • R410A GAS

Reviews

There are no reviews yet.

Be the first to review “PACi STANDARD 3Phase • S-100PK2E5B”

Downloads

No files uploaded.