PACi STANDARD 4 Way 90×90 Cassette Inverter+ 3 Phase • R410A GAS

From: £2,464.00£3,137.00


Note: All systems must be installed by Certified Installer.

Description

KitKIT-100PUY2E8DKIT-125PUY2E8DKIT-140PUY2E8D
Remote controllerCZ-RTC5BCZ-RTC5BCZ-RTC5B
Cooling capacityNominal (Min – Max)kW10.0 (2.7 – 11.5)12.5 (3.8 – 13.5)14.0 (3.3 – 15.5)
UK Cooling capacityTotal / SensiblekW10.6 / 8.812.2 / 9.914.1 / 10.7
EERNominal (Min – Max)W/W3.16 (5.09 – 2.74) B3.16 (4.22 – 2.77) B3.25 (3.93 – 267) A
SEERW/W6.60 A++6.206.39
PdesignkW10.012.514.0
Input power coolingNominal (Min – Max)kW3.16 (0.53 – 4.20)3.96 (0.90 – 4.88)4.31 (0.84 – 5.81)
Annual energy consumption (ErP)kWh/a530
Heating capacityNominal (Min – Max)kW10.0 (2.1 – 13.8)12.5 (3.4 – 15.0)14.0 (4.1 – 16.0)
UK Heating capacitykW12.614.015.9
Heating capacity at -7°C / -15°CkW— /—— /—— /—
COPNominal (Min – Max)W/W4.15 (5.12 – 3.45) A4.10 (4.66 – 3.41) A4.15 (4.56 – 3.08) A
SCOPW/W4.30 A+3.873.79
Pdesign at -10°CkW10.012.514.0
Input power heatingNominal (Min – Max)kW2.41 (0.41 – 4.00)3.05 (0.73 – 4.40)3.37 (0.90 – 5.20)
Annual energy consumption (ErP)kWh/a3256
Indoor unitS-100PU2E5BS-125PU2E5BS-140PU2E5B
Air volumeHi / Med / Lom³/min36.0 / 26.0 / 18.037.0 / 27.0 / 19.038.0 / 29.0 / 20.0
Sound pressureHi / Med / LodB(A)45 / 38 / 3246 / 39 / 3347 / 40 / 34
Dimension                          Indoor (H x W x D)mm319 x 840 x 840319 x 840 x 840319 x 840 x 840
Panel (H x W x D)mm33.5 x 950 x 95033.5 x 950 x 95033.5 x 950 x 950
Net weightIndoor / Panelkg25 / 525 / 525 / 5
Outdoor unitU-100PEY1E8U-125PEY1E8U-140PEY1E8
Power sourceV380 / 400 / 415380 / 400 / 415380 / 400 / 415
Recommended fuseA161616
Connectionmm²2.52.52.5
CurrentCoolA5.00 / 4.75 / 4.606.20 / 5.90 / 5.706.75 / 6.40 / 6.20
HeatA3.80 / 3.60 / 3.504.75 / 4.50 / 4.355.25 / 5.00 / 4.80
Air volumeCool / Heatm³/min76 / 6780 / 73135 / 120
Sound pressureCool / Heat (Hi)dB(A)54 / 5456 / 5654 / 53
DimensionH x W x Dmm996 x 940 x 340996 x 940 x 3401416 x 940 x 340
Net weightkg738598
Piping connectionsLiquid pipeInch (mm)3/8 (9.52)3/8 (9.52)3/8 (9.52)
Gas pipeInch (mm)5/8 (15.88)5/8 (15.88)5/8 (15.88)
Pipe length rangem5 ~ 505 ~ 505 ~ 50
Elevation difference (in/out)m303030
Pipe length for additional gasm303030
Additional gas amountg/m505050
Refrigerant (R410A)kg / TCO2 Eq.2.60 / 5.42883.20 / 6.68163.40 / 7.0992
Operating rangeCool Min ~ Max°C-10 ~ +43-10 ~ +43-10 ~ +43
Heat Min ~ Max°C-15 ~ +24-15 ~ +24-15 ~ +24

Additional information

PACi STANDARD 4 Way 90×90 Cassette Inverter+ 3 Phase • R410A GAS

, ,

Reviews

There are no reviews yet.

Be the first to review “PACi STANDARD 4 Way 90×90 Cassette Inverter+ 3 Phase • R410A GAS”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.