Description

KIT KIT-100PU2Z8 KIT-125PU2Z8 KIT-140PU2Z8
Remote controller CZ-RTC5B CZ-RTC5B CZ-RTC5B
Cooling capacity Nominal (Min – Max) kW 10.0 (3.0 – 11.5) 12.5 (3.2 – 13.5) 14.0 (3.3 – 15.0)
UK Cooling capacity Total / Sensible kW TBC TBC TBC
EER 1) Nominal (Min – Max) W/W 3.82 (5.36 – 2.88) A 3.58 (5.33 – 2.81) A 3.23 (5.32 – 2.73) A
SEER 2) W/W 6.70 A++ 6.73 6.49
Pdesign kW 10.0 12.5 14.0
Input power cooling Nominal (Min – Max) kW 2.62 (0.56 – 4.00) 3.49 (0.60 – 4.80) 4.34 (0.62 – 5.50)
Annual energy consumption (ErP) 3) kWh/a 521
Heating capacity Nominal (Min – Max) kW 10.0 (3.0 – 14.0) 12.5 (3.3 – 15.0) 14.0 (3.4 – 16.0)
UK Heating capacity kW TBC TBC TBC
Heating capacity at -7°C / -15°C 4) kW
COP 1) Nominal (Min – Max) W/W 4.93 (3.59 – 5.36) A 4.43 (3.57 – 5.50) A 4.18 (3.33 – 5.48) A
SCOP 2) W/W 4.40 A+ 4.01 3.89
Pdesign at -10°C kW 10.0 12.5 14.0
Input power heating Nominal (Min – Max) kW 2.03 (0.56 – 3.90) 2.82 (0.60 – 4.20) 3.35 (0.62 – 4.80)
Annual energy consumption (ErP) 3) kWh/a 3182
Indoor unit   S-100PU2E5B S-125PU2E5B S-140PU2E5B
Air volume Hi / Med / Lo m³/min 36.0 / 26.0 / 18.0 37.0 / 27.0 / 19.0 38.0 / 29.0 / 20.0
Moisture removal volume L/h 2.7 4.8 6.0
Sound pressure 5) Hi / Med / Lo dB(A) 45 / 38 / 32 46 / 39 / 33 47 / 40 / 34
Sound power Hi / Med / Lo dB 60 / 53 / 47 61 / 54 / 48 62 / 55 / 49
Dimension Indoor (H x W x D) mm 319 x 840 x 840 319 x 840 x 840 319 x 840 x 840
Panel (H x W x D) mm 33.5 x 950 x 950 33.5 x 950 x 950 33.5 x 950 x 950
Net weight Indoor / Panel kg 25 / 5 25 / 5 25 / 5
Outdoor unit   U-100PZ2E8 U-125PZ2E8 U-140PZ2E8
Power source V 380 / 400 / 415 380 / 400 / 415 380 / 400 / 415
Recommended fuse A
Connection mm²
Current Cool A 4.10 / 3.90 / 3.75 5.45 / 5.20 / 5.00 6.85 / 6.50 / 6.25
Heat A 3.15 / 3.00 / 2.90 4.40 / 4.15 / 4.00 5.25 / 4.95 / 4.80
Air volume Cool / Heat m³/min 76 / 70 86 / 78 89 / 83
Sound pressure Cool / Heat (Hi) dB(A) 52 / 52 55 / 55 56 / 56
Sound power Cool / Heat (Hi) dB 70 / 70 73 / 73 74 / 74
Dimension H x W x D mm 996 x 980 x 370 996 x 980 x 370 996 x 980 x 370
Net weight kg 90 94 94
Piping connections Liquid pipe Inch (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Gas pipe Inch (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)
Pipe length range m 5 ~ 50 5 ~ 50 5 ~ 50
Elevation difference (in/out) 6) m 30 30 30
Pipe length for additional gas m 30 30 30
Additional gas amount g/m 45 45 45
Refrigerant (R32) kg / TCO2 Eq. 2.60 / 1.755 2.98 / 2.0115 2.98 / 2.0115
Operating range Cool Min ~ Max °C -10 ~ +43 -10 ~ +43 -10 ~ +43
Heat Min ~ Max °C -15 ~ +24 -15 ~ +24 -15 ~ +24

Additional information

PACi STANDARD 4 Way 90×90 Cassette Inverter+ 3 Phase • R32 GAS

Up to 100 sq.m. room – S-100PU2E5B U-100PZ2E8, Up to 120 sq.m. room – S-125PU2E5B U-125PZ2E8, Up to 140 sq.m. room – S-140PU2E5B U-140PZ2E8

Reviews

There are no reviews yet.

Be the first to review “PACi STANDARD 4 Way 90×90 Cassette Inverter+ 3 Phase • R32 GAS”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.