Indoor Unit | S-71PU2E5B | S-100PU2E5B | S-125PU2E5B | S-140PU2E5B |
Outdoor Unit | U-71PZH2E8 | U-100PZH2E8 | U-125PZH2E8 | U-140PZH2E8 |
Nominal Cooling (Range) | kW | 7.1 (2.2 – 9.0) | 10.0 (3.1 – 12.5) | 12.5 (3.2 – 14.0) | 14.0 (3.3 – 16.0) |
UK Cooling (Total – Sensible) | kW | 8.1 – 5.4 | 10.7 – 7.6 | 12.6 – 8.4 | 13.9 – 9.2 |
Nominal Heating (Range) | kW | 8.0 (2 – 9) | 11.2 (3.3 – 14) | 14.0 (3.2 – 16) | 16.0 (3.5 – 18) |
UK Heating | kW | 8.1 | 12.5 | 14.4 | 16.2 |
SEER – SCOP (Cooling – Heating) | 7.7 – 4.8 | 7.7 – 4.9 | 7.64 – 4.73 | 7.22 – 4.60 |
Energy Efficiency Class (Cool / Heat) | A++ / A++ | A++ / A++ | – | – |
EER – COP (Cooling – Heating) | 4.06 – 4.30 | 4.41 – 5.00 | 3.80 – 4.61 | 3.41 – 4.30 |
Energy Label (Cooling / Heating) | TBC | TBC | TBC | TBC |
Annual Electricity Cons. (Cool – Heat) | kWh/a | 327 – 1517 | 455 – 2286 | TBC | TBC |
Pdesign (Cooling – Heating at -10°C) | kW | 7.1 – 5.2 | 10.0 – 8.0 | 12.5 – 9.5 | 14.0 – 10.6 |
Heating Capacity at -7°C / -15°C | kW | TBC | TBC | TBC | TBC |
Operating Range – Cooling | °C | -15°C to 46°C | -15°C to 46°C | -15°C to 46°C | -15°C to 46°C |
Operating Range – Heating | °C | -20°C to 24°C | -20°C to 24°C | -20°C to 24°C | -20°C to 24°C |
Indoor Unit (Grille) Dimensions H-W-D | mm | 256(33.5)x840(950)x840(950) | 319(33.5)x840(950)x840(950) | 319(33.5)x840(950)x840(950) | 319(33.5)x840(950)x840(950) |
Outdoor Unit Dimensions (H-W-D) | mm | 996 x 940 x 340 | 1416 x 940 x 340 | 1416 x 940 x 340 | 1416 x 940 x 340 |
Weight (Indoor (Grille) – Outdoor) | kg | 20 (5) – 68 | 25 (5) – 99 | 25 (5) – 99 | 25 (5) – 101 |
Indoor Unit Airflow Rate (L-M-H) | l/s | 217 – 260 – 360 | 300 – 430 – 600 | 317 – 450 – 617 | 330 – 483 – 630 |
Moisture Removal Volume | l/h | 2.5 | 2.5 | 4.8 | 6.0 |
Outdoor Unit Airflow Rate (Cool – Heat) | l/s | 1016 – 1000 | 1960 – 1800 | 2083 – 2033 | 2150 – 1933 |
Indoor Sound Pressure (L-M-H) | dB(A) | 28 – 31 – 37 | 32 – 38 – 45 | 33 – 39 – 46 | 34 – 40 – 47 |
Outdoor Sound Pressure (Cool – Heat) | dB(A) | 48 – 50 | 52 – 52 | 53 – 53 | 54 – 54 |
Pipe Sizes (Gas – Liquid) | in | 5/8″ – 3/8″ | 5/8″ – 3/8″ | 5/8″ – 3/8″ | 5/8″ – 3/8″ |
Pipe Limits (Min-Max Run/Height Diff.) | m | 5 – 50 / 15 – 30 | 5 – 85 / 15 – 30 | 5 – 75 / 15 – 30* | 5 – 85 / 15 – 30* |
Pre-Charged For | m | 30 | 30 | 30 | 30 |
R32 Charge (Factory – Additional) | kg – g/m | 1.95 – 45 | 3.05 – 45 | 3.05 – 45 | TBC |
GWP (Tonnes CO2 Equivalent) | 1.316 | 2.059 | 2.059 | TBC |
Suitable For Replacement Tech. | Yes | Yes | Yes | Yes |
Indoor Drain Connection | mm | VP25 (32mm OD) | VP25 (32mm OD) | VP25 (32mm OD) | VP25 (32mm OD) |
Power Supply (Outdoor / Indoor) | V-Ph-Hz | 400 – 3 – 50 / 230 – 1 – 50 | 400 – 3 – 50 / 230 – 1 – 50 | 400 – 3 – 50 / 230 – 1 – 50 | 400 – 3 – 50 / 230 – 1 – 50 |
Interconnecting Cables | 2 core** | 2 core** | 2 core** | 2 core** |
Running Current (Cooling – Heating) | A | 2.65 – 2.80 | 3.35 – 3.30 | 4.90 – 4.50 | 6.15 – 5.55 |
Input Power (Cooling – Heating) | kW | 1.75 – 1.86 | 2.27 – 2.24 | 3.29 – 3.04 | 4.11 – 3.72 |
Suggested Fuse Size (Outdoor / Indoor) | A | 10A Per Phase / 5A | 13A Per Phase / 5A | 15A Per Phase / 5A | 15A Per Phase / 5A |