MXZ-F – OUTDOOR UNITSMXZ-3F54VFMXZ-3F68VF
NUMBER OF CONNECTABLE INDOOR UNITS2 – 32 – 3
CAPACITY (kW)Heating (nominal)7.0 (2.6-9.0)8.6 (2.6-10.6)
Cooling (nominal)5.4 (2.9-6.8)6.8 (2.9-8.4)
Heating (UK)5.81 (2.16-7.47)7.14 (2.16-8.80)
Cooling (UK)5.3 (2.85-6.67)6.66 (2.84-8.23)
COP / EER (nominal)*14.60 / 4.104.50 / 3.70
SCOP / SEER (BS EN14825)4.61 / 8.524.12 / 7.96
ErP ENERGY EFFICIENCY CLASSHeating/CoolingA++ / A+++A+ / A++
MAX AIRFLOW (m3/min)Heating/Cooling43.0 / 42.143.0 / 42.1
SOUND PRESSURE LEVEL (dBA)Heating/Cooling50 / 4653 / 48
SOUND POWER LEVEL (dBA)Cooling5963
DIMENSIONS (mm)Width x Depth x Height840 x 330 x 710840 x 330 x 710
WEIGHT (kg)5858
ELECTRICAL SUPPLY220-240v, 50Hz220-240v, 50Hz
PHASESingleSingle
POWER INPUT (kW)Heating/Cooling (nominal)1.52 / 1.321.91 / 1.84
Heating/Cooling (UK)1.38 / 1.061.73 / 1.47
STARTING CURRENT (A)7.010.5
RUNNING CURRENT (A)Heating/Cooling [MAX]7.0 / 5.9 [18.0]10.5 / 9.6 [18.0]
INTERCONNECTING CABLE No. CORES4 Core4 Core
TOTAL PIPE LENGTH (m)5060
MAX PIPE LENGTH PER INDOOR UNIT (m)2525
MAX HEIGHT DIFFERENCE (m)15 (10 if OU higher than IU)15 (10 if OU higher than IU)
CHARGE REFRIGERANT (kg) /CO2 EQUIVALENT (t) – R32 (GWP 675)1.40 / 0.95 (50m)1.40 / 0.95 (60m)
MAX ADDITIONAL REFRIGERANT (kg) /CO2 EQUIVALENT (t) – R32 (GWP 675)2.40 / 1.622.40 / 1.62
FUSE RATING (BS88) – HRC (A)2525