MXZ-E/D R410A Outdoor Units – Up to 5 Rooms

From: £2,267.00 ex. VAT


Note: All systems must be installed by Certified Installer.

Description

MXZ-E/D – OUTDOOR UNITS MXZ-5E102VA
NUMBER OF CONNECTABLE INDOOR UNITS 2 – 5
CAPACITY (kW) Heating (nominal) 10.5 (4.1-14.0)
Cooling (nominal) 10.2 (3.9-11.0)
Heating (UK) 8.7 (3.40-11.63)
Cooling (UK) 10.1 (3.86-10.90)
COP / EER (nominal)*1 4.49 / 3.24
SCOP (ƞsh) / SEER (ƞsc) (BS EN14825) 4.20 / 6.6
ErP ENERGY EFFICIENCY CLASS Heating/Cooling A+ / A++
MAX AIRFLOW (m3/min) Heating/Cooling 67.6 / 55.7
SOUND PRESSURE LEVEL (dBA) Heating/Cooling 56 / 52
SOUND POWER LEVEL (dBA) Cooling 65
DIMENSIONS (mm) Width x Depth x Height 950 x 330 x 796
WEIGHT (kg) 63
ELECTRICAL SUPPLY 220-240v, 50Hz
PHASE Single
POWER INPUT (kW) Heating/Cooling (nominal) 2.34 / 3.15
Heating/Cooling (UK) 2.15 / 2.99
STARTING CURRENT (A) 13.8
RUNNING CURRENT (A) Heating/Cooling [MAX] 12.7 / 17.2 [21.4]
INTERCONNECTING CABLE No. CORES 4 Core
TOTAL PIPE LENGTH (m) 80
MAX PIPE LENGTH PER INDOOR UNIT (m) 25
MAX HEIGHT DIFFERENCE (m) 15 (10 if OU higher than IU)
CHARGE REFRIGERANT (kg) /CO2 EQUIVALENT (t) – R410A (GWP 2088) 2.99 / 6.25 (0m)
MAX ADDITIONAL REFRIGERANT (kg) /CO2 EQUIVALENT (t) – R410A (GWP 2088) 1.60 / 3.35
FUSE RATING (BS88) – HRC (A) 25

Additional information

MXZ-E/D R410A Outdoor Units – Up to 5 Rooms

Reviews

There are no reviews yet.

Be the first to review “MXZ-E/D R410A Outdoor Units – Up to 5 Rooms”

Downloads