MU5M Outdoor Units R410A – Up to 5 Rooms

From: £1,638.00£2,402.00 ex. VAT


Note: All systems must be installed by Certified Installer.

Description

OUTDOOR UNIT MU5M30 U44 MU5M40 UO2
Compressor                       Type Twin Rotary Twin Rotary
Capacity * Cooling Min/Nom/Max kW 1.3/8.8/10.6 0.9 / 11.2 / 13.5
Heating Min/Nom/Max kW 1.5/10.1/12.1 1.0 / 12.5 / 15.0
Low Temperature Capacity    Heating -7°C Max kW 7.1 11.0
Power Input * Cooling Min/Nom/Max kW 0.4/2.3/3.6 0.8 / 2.7 / 4.2
Heating Min/Nom/Max kW 0.6/2.3/3.7 0.8 / 2.8 / 4.5
Running Current Cooling Min/Nom/Max A 1.9/10.2/16.2 3.5 / 12.1 / 18.4
Heating Min/Nom/Max A 2.8/10.4/16.8 3.6 / 12.5 / 19.7
EER 3.90 4.10
COP 4.41 4.45
SEER 7.00 5.80
SCOP 4.00 3.81
Pdesign (@-10°C) kW 7.2 11.8
Seasonal Energy Label          Cooling/Heating A++/A+ A+ / A
Annual Energy Consumption  Cooling/Heating 440 / 2520 643 / 4,236
Airflow Rate                      Nom m2/min 60 90
Sound Pressure Cooling Nom dBA 50 53
Heating Nom dBA 54 55
Sound Power                      Cooling Max dBA 66 67
Dimensions                        W x H x D mm 950 x 834 x 330 950 × 1,170 × 330
Net Weight Kg 61 84.0
Refrigerant Type / Charge Kg- TCO R410A R410A
Charge Kg 3.2 3,8
Additional Charge g/m 20 20
GWP 2,087.5 2,087.5
t-CO2 eq 6.7 7.9
Operation Range(Outdoor) Cooling Min~Max °C DB -10~48 -10 ~ 48
Heating Min~Max °C WB -18~18 -18 ~ 18
Power Supply Ø/V/Hz 1/220-240/50 1 / 220-240 / 50
Power Supply Cable No.xmm2 3Cx2.5 3C × 3.5
Transmission Cable No.xmm2 4Cx0.75 4C × 0.75
Maximum Running Current A 16.7 21.2
Maximum Circuit Breaker Rating A 25 30
Piping Length Total m 75 85
Piping Length per Branch Max m 25 25
Piping Elevation Difference IDU-ODU Max m 15 15
IDU-IDU Max m 7.5 7.5
Piping Connection Liquid mmxNo. Ø6.35 (1/4)x5 Ø6.35 (1/4) × 5
Gas mmxNo. Ø9.52 (3/8)x5 Ø9.52 (3/8) × 5

Additional information

MU5M (OU) – Up to 5 Rooms

,

Reviews

There are no reviews yet.

Be the first to review “MU5M Outdoor Units R410A – Up to 5 Rooms”

Downloads

No files uploaded.