Sale!

PACi STANDARD Low Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS

Compare

From: £1,567.80 - £2,093.65 ex. VAT

Clear

Description

KIT KIT-100PNY1E8C KIT-125PNY1E8C KIT-140PNY1E8C
Remote controller CZ-RTC5B CZ-RTC5B CZ-RTC5B
Cooling capacity Nominal (Min – Max) kW 10.0 (2.7 – 11.5) 12.5 (3.8 – 13.5) 14.0 (3.3 – 15.5)
UK Cooling capacity Total / Sensible kW 10.6 / 8.5 12.2 / 9.3 14.1 / 10.5
EER Nominal (Min – Max) W/W 2.81 (4.74 – 2.67) C 2.81 (4.00 – 2.60) C 2.98 (3.93 – 2.58) C
SEER W/W 5.20 A 4.95 5.18
Pdesign kW 10.0 12.5 14.0
Input power cooling Nominal (Min – Max) kW 3.56 (0.57 – 4.30) 4.45 (0.95 – 5.20) 4.70 (0.84 – 6.00)
Annual energy consumption (ErP) kWh/a 673
Heating capacity Nominal (Min – Max) kW 10.0 (2.1 – 13.8) 12.5 (3.4 – 15.0) 14.0 (4.1 – 16.0)
UK Heating capacity kW 12.9 14.0 15.9
Heating capacity at -7°C /-15°C kW 9.97 10.97 13.35
COP Nominal (Min – Max) W/W 3.41 (4.67 – 3.37) B 3.41 (4.36 – 3.26) B 3.52 (4.56 – 3.08) B
SCOP W/W 3.80 A 3.52 3.52
Pdesign at -10°C kW 7.6 12.5 14.0
Input power heating Nominal (Min – Max) kW 2.94 (0.45 – 4.10) 3.67 (0.78 – 4.60) 3.88 (1.05 – 5.40)
Annual energy consumption (ErP) kWh/a 2800
Indoor unit S-100PN1E5A S-125PN1E5A S-140PN1E5A
External static pressure Nominal (Min – Max) Pa 50 (10 – 80) 50 (10 – 80) 50 (10 – 80)
Air volume Cool / Heat m³/min 36 / 33 / 26 38 / 35 / 28 40 / 37 / 30
Sound pressure Hi / Med / Lo dB(A) 44 / 42 / 37 45 / 43 / 38 46 / 44 / 39
Dimension H x W x D mm 250 x 1200 x 650 250 x 1200 x 650 250 x 1200 x 650
Net weight kg 41 41 41
Outdoor unit U-100PEY1E8 U-125PEY1E8 U-140PEY1E8
Power source V 380 / 400 / 415 380 / 400 / 415 380 / 400 / 415
Recommended fuse A 16 16 16
Connection mm² 2.5 2.5 2.5
Current Cool A 5.45 / 5.20 / 5.05 6.85 / 6.50 / 6.25 7.05 / 6.50 / 6.45
Heat A 4.45 / 4.25 / 4.10 5.55 / 5.30 / 5.10 5.90 / 5.60 / 5.40
Air volume Cool / Heat m³/min 76 / 67 80 / 73 135 / 120
Sound pressure Cool / Heat (Hi) dB(A) 54 / 54 56 / 56 54 / 53
Dimension H x W x D mm 996 x 940 x 340 996 x 940 x 340 1416 x 940 x 340
Net weight kg 73 85 98
Piping connections Liquid pipe Inch (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Gas pipe Inch (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)
Pipe length range m 5 ~ 50 5 ~ 50 5 ~ 50
Elevation difference (in/out) m 30 30 30
Pipe length for additional gas m 30 30 30
Additional gas amount g/m 50 50 50
Refrigerant (R410A) kg / TCO2 Eq. 2.60 / 5.4288 3.20 / 6.6816 3.40 / 7.0992
Operating range  Cool Min ~ Max °C -10 ~ +43 -10 ~ +43 -10 ~ +43
Heat Min ~ Max °C -15 ~ +24 -15 ~ +24 -15 ~ +24

Additional information

PACi STANDARD Low Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS

Up to 100 sq.m. room – S-100PN1E5A U-100PEY1E8, Up to 120 sq.m. room – S-125PN1E5A U-125PEY1E8, Up to 140 sq.m. room – S-140PN1E5A U-140PEY1E8

Reviews

There are no reviews yet.

Be the first to review “PACi STANDARD Low Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.