PACi ELITE Low Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS

From: £2,465.00£3,935.00


Note: All systems must be installed by Certified Installer.

Description

KITKIT-71PN1E8CKIT-100PN1E8CKIT-125PN1E8CKIT-140PN1E8C
Remote controllerCZ-RTC5BCZ-RTC5BCZ-RTC5BCZ-RTC5B
Cooling capacityNominal (Min – Max)kW7.1 (2.5 – 8.0)10.0 (3.3 – 12.5)12.5 (3.3 – 14.0)14.0 (3.3 – 15.5)
UK Cooling capacityTotal / SensiblekW7.9 / 6.211.4 / 9.212.7 / 9.714.1 / 10.5
EERNominal (Min – Max)W/W3.30 (3.79 – 2.91) A3.75 (3.79 – 3.29) A3.21 (3.30 – 2.92) A3.01 (3.30 – 2.50) A
SEERW/W5.10 A5.60 A+5.445.27
PdesignkW7.110.012.514.0
Input power coolingNominal (Min – Max)kW2.15 (0.66 – 2.75)2.67 (0.87 – 3.80)3.89 (1.00 – 4.80)4.65 (1.00 – 6.20)
Annual energy consumption (ErP)kWh/a487621
Heating capacityNominal (Min – Max)kW8.0 (2.0 – 9.0)11.2 (4.1 – 14.0)14.0 (4.1 – 16.0)16.0 (4.1 – 18.0)
UK Heating capacitykW8.114.015.917.8
Heating capacity at -7°C /-15°CkW7.5212.0413.4814.24
COPNominal (Min – Max)W/W3.54 (3.33 – 3.00) B3.80 (4.18 – 3.11) A3.61 (3.90 – 2.96) A3.41 (3.90 – 2.95) B
SCOPW/W3.80 A3.80 A3.663.58
Pdesign at -10°CkW6.210.012.514.0
Input power heatingNominal (Min – Max)kW2.26 (0.60 – 3.00)2.95 (0.98 – 4.50)3.88 (1.05 – 5.40)4.69 (1.05 – 6.10)
Annual energy consumption (ErP)kWh/a22843684
Indoor unitS-71PN1E5AS-100PN1E5AS-125PN1E5AS-140PN1E5A
External static pressureNominal (Min – Max)Pa50 (10 – 80)50 (10 – 80)50 (10 – 80)50 (10 – 80)
Air volumeCool / Heatm³/min22 / 20 / 1636 / 33 / 2638 / 35 / 2840 / 37 / 30
Sound pressureHi / Med / LodB(A)43 / 41 / 3644 / 42 / 3745 / 43 / 3846 / 44 / 39
DimensionH x W x Dmm250 x 1000 x 650250 x 1200 x 650250 x 1200 x 650250 x 1200 x 650
Net weightkg32414141
Outdoor unitU-71PE1E8AU-100PE1E8AU-125PE1E8AU-140PE1E8A
Power sourceV380 / 400 / 415380 / 400 / 415380 / 400 / 415380 / 400 / 415
Recommended fuseA16161616
Connectionmm²2.52.52.52.5
CurrentCoolA3.25 / 3.10 / 3.003.95 / 3.75 / 3.605.80 / 5.50 / 5.306.95 / 6.60 / 6.35
HeatA3.35 / 3.20 / 3.104.35 / 4.15 / 4.005.80 / 5.50 / 5.307.00 / 6.65 / 6.45
Air volumeCool / Heatm³/min60 / 60110 / 95130 / 110135 / 120
Sound pressureCool / Heat (Hi)dB(A)48 / 5052 / 5253 / 5354 / 55
DimensionH x W x Dmm996 x 940 x 3401416 x 940 x 3401416 x 940 x 3401416 x 940 x 340
Net weightkg71989898
Piping connectionsLiquid pipeInch (mm)3/8 (9.52)3/8 (9.52)3/8 (9.52)3/8 (9.52)
Gas pipeInch (mm)5/8 (15.88)5/8 (15.88)5/8 (15.88)5/8 (15.88)
Pipe length rangem5 ~ 505 ~ 755 ~ 755 ~ 75
Elevation difference (in/out)m30303030
Pipe length for additional gasm30303030
Additional gas amountg/m50505050
Refrigerant (R410A)kg / TCO2 Eq.2.35 / 4.90683.40 / 7.09923.40 / 7.09923.40 / 7.0992
Operating rangeCool Min ~ Max°C-15 ~ +46-15 ~ +46-15 ~ +46-15 ~ +46
Heat Min ~ Max°C-20 ~ +24-20 ~ +24-20 ~ +24-20 ~ +24

Additional information

PACi ELITE Low Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS

, , ,

Reviews

There are no reviews yet.

Be the first to review “PACi ELITE Low Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.