PACi ELITE Low Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS

From: £2,465.00£3,935.00 ex. VAT


Note: All systems must be installed by Certified Installer.

Description

KIT KIT-71PN1E8C KIT-100PN1E8C KIT-125PN1E8C KIT-140PN1E8C
Remote controller CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B
Cooling capacity Nominal (Min – Max) kW 7.1 (2.5 – 8.0) 10.0 (3.3 – 12.5) 12.5 (3.3 – 14.0) 14.0 (3.3 – 15.5)
UK Cooling capacity Total / Sensible kW 7.9 / 6.2 11.4 / 9.2 12.7 / 9.7 14.1 / 10.5
EER Nominal (Min – Max) W/W 3.30 (3.79 – 2.91) A 3.75 (3.79 – 3.29) A 3.21 (3.30 – 2.92) A 3.01 (3.30 – 2.50) A
SEER W/W 5.10 A 5.60 A+ 5.44 5.27
Pdesign kW 7.1 10.0 12.5 14.0
Input power cooling Nominal (Min – Max) kW 2.15 (0.66 – 2.75) 2.67 (0.87 – 3.80) 3.89 (1.00 – 4.80) 4.65 (1.00 – 6.20)
Annual energy consumption (ErP) kWh/a 487 621
Heating capacity Nominal (Min – Max) kW 8.0 (2.0 – 9.0) 11.2 (4.1 – 14.0) 14.0 (4.1 – 16.0) 16.0 (4.1 – 18.0)
UK Heating capacity kW 8.1 14.0 15.9 17.8
Heating capacity at -7°C /-15°C kW 7.52 12.04 13.48 14.24
COP Nominal (Min – Max) W/W 3.54 (3.33 – 3.00) B 3.80 (4.18 – 3.11) A 3.61 (3.90 – 2.96) A 3.41 (3.90 – 2.95) B
SCOP W/W 3.80 A 3.80 A 3.66 3.58
Pdesign at -10°C kW 6.2 10.0 12.5 14.0
Input power heating Nominal (Min – Max) kW 2.26 (0.60 – 3.00) 2.95 (0.98 – 4.50) 3.88 (1.05 – 5.40) 4.69 (1.05 – 6.10)
Annual energy consumption (ErP) kWh/a 2284 3684
Indoor unit S-71PN1E5A S-100PN1E5A S-125PN1E5A S-140PN1E5A
External static pressure Nominal (Min – Max) Pa 50 (10 – 80) 50 (10 – 80) 50 (10 – 80) 50 (10 – 80)
Air volume Cool / Heat m³/min 22 / 20 / 16 36 / 33 / 26 38 / 35 / 28 40 / 37 / 30
Sound pressure Hi / Med / Lo dB(A) 43 / 41 / 36 44 / 42 / 37 45 / 43 / 38 46 / 44 / 39
Dimension H x W x D mm 250 x 1000 x 650 250 x 1200 x 650 250 x 1200 x 650 250 x 1200 x 650
Net weight kg 32 41 41 41
Outdoor unit U-71PE1E8A U-100PE1E8A U-125PE1E8A U-140PE1E8A
Power source V 380 / 400 / 415 380 / 400 / 415 380 / 400 / 415 380 / 400 / 415
Recommended fuse A 16 16 16 16
Connection mm² 2.5 2.5 2.5 2.5
Current Cool A 3.25 / 3.10 / 3.00 3.95 / 3.75 / 3.60 5.80 / 5.50 / 5.30 6.95 / 6.60 / 6.35
Heat A 3.35 / 3.20 / 3.10 4.35 / 4.15 / 4.00 5.80 / 5.50 / 5.30 7.00 / 6.65 / 6.45
Air volume Cool / Heat m³/min 60 / 60 110 / 95 130 / 110 135 / 120
Sound pressure Cool / Heat (Hi) dB(A) 48 / 50 52 / 52 53 / 53 54 / 55
Dimension H x W x D mm 996 x 940 x 340 1416 x 940 x 340 1416 x 940 x 340 1416 x 940 x 340
Net weight kg 71 98 98 98
Piping connections Liquid pipe Inch (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Gas pipe Inch (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)
Pipe length range m 5 ~ 50 5 ~ 75 5 ~ 75 5 ~ 75
Elevation difference (in/out) m 30 30 30 30
Pipe length for additional gas m 30 30 30 30
Additional gas amount g/m 50 50 50 50
Refrigerant (R410A) kg / TCO2 Eq. 2.35 / 4.9068 3.40 / 7.0992 3.40 / 7.0992 3.40 / 7.0992
Operating range Cool Min ~ Max °C -15 ~ +46 -15 ~ +46 -15 ~ +46 -15 ~ +46
Heat Min ~ Max °C -20 ~ +24 -20 ~ +24 -20 ~ +24 -20 ~ +24

Additional information

PACi ELITE Low Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS

, , ,

Reviews

There are no reviews yet.

Be the first to review “PACi ELITE Low Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS”

Downloads

No files uploaded.