KIT KIT-60PFY1E5D KIT-71PFY1E5D KIT-100PFY1E5D KIT-125PFY1E5D
Remote controller CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B
Cooling capacity Nominal (Min – Max) kW 6.0 (2.0 – 7.1) 7.1 (2.0 – 7.7) 10.0 (2.7 – 11.5) 12.5 (3.8 – 13.5)
UK Cooling capacity Total / Sensible kW 6.8 / 5.4 7.4 / 5.7 10.6 / 8.7 12.2 / 9.2
EER Nominal (Min – Max) W/W 3.35 (5.97 – 2.85) A 2.76 (5.97 – 2.48) D 3.01 (5.09 – 2.74) B 3.05 (4.22 – 2.70) B
SEER W/W 5.50 A 5.40 A 5.40 A 5.11
Pdesign kW 6.0 7.1 10.0 12.5
Input power cooling Nominal (Min – Max) kW 1.79 (0.34 – 2.49) 2.57 (0.34 – 3.10) 3.32 (0.53 – 4.20) 4.10 (0.90 – 5.00)
Annual energy consumption (ErP) kWh/a 382 460 648
Heating capacity Nominal (Min – Max) kW 6.0 (1.8 – 7.0) 7.1 (1.8 – 8.1) 10.0 (2.1 – 13.8) 12.5 (3.4 – 15.0)
UK Heating capacity kW 6.8 7.9 12.9 14.0
Heating capacity at -7°C /-15°C kW — /— — /— — /— 11.00 /—
COP Nominal (Min – Max) W/W 4.38 (6.32 – 4.12) A 4.10 (6.32 – 3.68) A 3.80 (5.12 – 3.45) A 3.82 (4.66 – 3.41) A
SCOP W/W 4.00 A+ 4.00 A+ 3.80 A 3.60
Pdesign at -10°C kW 6.0 6.0 9.5 12.5
Input power heating Nominal (Min – Max) kW 1.37 (0.29 – 1.70) 1.73 (0.29 – 2.20) 2.63 (0.41 – 4.00) 3.27 (0.73 – 4.40)
Annual energy consumption (ErP) kWh/a 2100 2100 3500
Indoor unit S-60PF1E5B S-71PF1E5B S-100PF1E5B S-125PF1E5B
External static pressure Nominal (Min – Max) Pa 70 (10 – 150) 70 (10 – 150) 100 (10 – 150) 100 (10 – 150)
Air volume Hi / Med / Lo m³/min 21 / 19 / 15 21 / 19 / 15 32 / 26 / 21 34 / 29 / 23
Sound pressure Hi / Med / Lo dB(A) 35 / 32 / 26 35 / 32 / 26 38 / 34 / 31 39 / 35 / 32
Dimension H x W x D mm 290 x 1000 x 700 290 x 1000 x 700 290 x 1400 x 700 290 x 1400 x 700
Net weight kg 33 33 45 45
Outdoor unit U-60PEY2E5 U-71PEY2E5 U-100PEY1E5 U-125PEY1E5
Power source V 220 / 230 / 240 220 / 230 / 240 220 / 230 / 240 220 / 230 / 240
Recommended fuse A 25 30
Connection mm² 4 6
Current Cool A 8.40 / 8.10 / 7.75 12.20 / 11.70 / 11.20 15.10 / 14.50 / 13.90 18.80 / 18.00 / 17.20
Heat A 6.30 / 6.05 / 5.80 8.15 / 7.80 / 7.45 11.80 / 11.20 / 10.70 14.60 / 14.00 / 13.40
Air volume Cool / Heat m³/min 38 / 41 44 / 41 76 / 67 80 / 73
Sound pressure Cool / Heat (Hi) dB(A) 46 / 48 49 / 49 54 / 54 56 / 56
Dimension H x W x D mm 619 x 799 x 299 619 x 799 x 299 996 x 940 x 340 996 x 940 x 340
Net weight kg 40 40 73 85
Piping connections Liquid pipe Inch (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Gas pipe Inch (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)
Pipe length range m 3 ~ 40 3 ~ 40 5 ~ 50 5 ~ 50
Elevation difference (in/out) m 30 30 30 30
Pipe length for additional gas m 30 30 30 30
Additional gas amount g/m 40 40 50 50
Refrigerant (R410A) kg / TCO2 Eq. 1.95 / 4.0716 1.95 / 4.0716 2.60 / 5.4288 3.20 / 6.6816
Operating range Cool Min ~ Max °C -10 ~ +43 -10 ~ +43 -10 ~ +43 -10 ~ +43
Heat Min ~ Max °C -15 ~ +24 -15 ~ +24 -15 ~ +24 -15 ~ +24

Additional information

PACi STANDARD High Static Pressure Hide Away Inverter+ Single Phase • R410A GAS

, , ,

Reviews

There are no reviews yet.

Be the first to review “PACi STANDARD High Static Pressure Hide Away Inverter+ Single Phase • R410A GAS”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.