PACi ELITE High Static Pressure Hide Away Inverter+ Single Phase • R410A GAS

Compare

From: £1,603.00£3,704.00 ex. VAT

Clear

Description

KITKIT-36PF1E5DKIT-50PF1E5DKIT-60PF1E5DKIT-71PF1E5DKIT-100PF1E5DKIT-125PF1E5DKIT-140PF1E5D
Remote controllerCZ-RTC5BCZ-RTC5BCZ-RTC5BCZ-RTC5BCZ-RTC5BCZ-RTC5BCZ-RTC5B
Cooling capacityNominal(Min-Max)kW3.6 (1.5 – 4.0)5.0 (1.5 – 5.6)6.0 (2.0 – 7.1)7.1 (2.5 – 8.0)10.0 (3.3 – 12.5)12.5 (3.3 – 14.0)14.0 (3.3 – 15.5)
UK Cooling capacityTotal/SensiblekW4.0 / 3.45.5 / 4.36.8 / 5.47.9 / 6.011.4 / 9.312.7 / 9.614.1 / 10.3
EERNominal(Min-Max)W/W4.44(5.17-4.00)A3.85(5.17-3.50)A3.64(5.97-3.02)A3.84(4.72-3.02)A4.10(3.93-3.38)A3.50(3.93-3.04)A3.25(3.93-2.58)A
SEERW/W5.70 A+5.70 A+6.10 A++6.40 A++5.80 A+5.575.41
PdesignkW3.65.06.07.110.012.514.0
Input power coolingNominal(Min-Max)kW0.81(0.29-1.00)1.30(0.29-1.60)1.65(0.34-2.35)1.85(0.53-2.65)2.44(0.84-3.70)3.57(0.84-4.60)4.31(0.84-6.00)
Annual energy consumption (ErP)kWh/a221307344388603
Heating capacityNominal(Min-Max)kW4.0(1.5 – 5.0)5.6(1.5 – 6.5)7.0(1.8 – 8.0)8.0(2.0 – 9.0)11.2(4.1 – 14.0)14.0(4.1 – 16.0)16.0(4.1 – 18.0)
UK Heating capacitykW4.66.37.88.114.015.917.8
Heating capacity at -7°C / -15°CkW— /—— /—— /—— /—— /—— /—12.32 /—
COPNominal(Min-Max)W/W4.55(6.25-4.17)A4.03(6.25-3.71)A4.00(6.32-3.81)A3.85(4.17-3.10)A4.31(4.56-3.18)A4.02(4.56-3.08)A3.60(4.56-3.05)A
SCOPW/W3.90 A3.90 A4.00 A+4.00 A+3.80 A3.723.63
Pdesign at -10°CkW3.64.06.07.110.012.514.0
Input power heatingNominal(Min-Max)kW0.88(0.24-1.20)1.39(0.24-1.75)1.75(0.29-2.10)2.08(0.48-2.90)2.60(0.90-4.40)3.48(0.90-5.20)4.44(0.90-5.90)
Annual energy consumption (ErP)kWh/a12921436210024853684
Indoor unitS-36PF1E5BS-50PF1E5BS-60PF1E5BS-71PF1E5BS-100PF1E5BS-125PF1E5BS-140PF1E5B
External static pressureNominal(Min-Max)Pa70 (10 – 150)70 (10 – 150)70 (10 – 150)70 (10 – 150)100 (10 – 150)100 (10 – 150)100 (10 – 150)
Air volumeHi/Med/Lom³/min14 / 13 /1016 / 15 / 1221 / 19 / 1521 / 19 / 1532 / 26 / 2134 / 29 / 2336 / 32 / 25
Sound pressureHi/Med/LodB(A)33 / 29 / 2534 / 30 / 2635 / 32 / 2635 / 32 / 2638 / 34 / 3139 / 35 / 3240 / 36 / 33
DimensionHxWxDmm290x800x700290x800x700290x1000x700290x1000x700290x1400x700290x1400x700290x1400x700
Net weightkg28283333454545
Outdoor unitU-36PE2E5AU-50PE2E5AU-60PE2E5AU-71PE1E5AU-100PE1E5AU-125PE1E5AU-140PE1E5A
Power sourceV220 / 230 / 240220 / 230 / 240220 / 230 / 240220 / 230 / 240220 / 230 / 240220 / 230 / 240220 / 230 / 240
Recommended fuseA20253016
Connectionmm²2.54.06.02.5
CurrentCool
Heat
A
A
3.70/3.50/3.40
4.05/3.85/3.70
5.80/5.60/5.30
6.30/6.05/5.80
7.70/7.40/7.10
8.25/7.85/7.55
8.90/8.60/8.30
9.90/9.50/9.20
11.00/10.60/10.30
11.60/11.20/10.70
16.60/15.90/15.30
16.30/15.80/15.10
20.10/19.30/18.60
19.90/19.10/18.40
Air volumeCool/Heatm³/min38 / 3838 / 4138 / 4160 / 60110 / 95130 / 110135 / 120
Sound pressureCool/Heat(Hi)dB(A)45 / 4646 / 4846 / 4948 / 5052 / 5253 / 5354 / 55
DimensionHxWxDmm619 x 799 x 299619 x 799 x 299619 x 799 x 299996 x 940 x 3401416 x 940 x 3401416 x 940 x 3401416 x 940 x 340
Net weightkg39394069989898
Piping connectionsLiquid pipeInch (mm)1/4 (6.35)1/4 (6.35)3/8 (9.52)3/8 (9.52)3/8 (9.52)3/8 (9.52)3/8 (9.52)
Gas pipeInch (mm)1/2 (12.70)1/2 (12.70)5/8 (15.88)5/8 (15.88)5/8 (15.88)5/8 (15.88)5/8 (15.88)
Pipe length rangem3 ~ 403 ~ 403 ~ 405 ~ 505 ~ 755 ~ 755 ~ 75
Elevation difference (in/out)m30303030303030
Pipe length for additional gasm30303030303030
Additional gas amountg/m20204050505050
Refrigerant (R410A)kg / TCO2 Eq.1.40 / 2.92321.40 / 2.92321.95 / 4.07162.35 / 4.90683.40 / 7.09923.40 / 7.09923.40 / 7.0992
Operating rangeCool Min~Max°C-15 ~ +46-15 ~ +46-15 ~ +46-15 ~ +46-15 ~ +46-15 ~ +46-15 ~ +46
Heat Min~Max°C-20 ~ +24-20 ~ +24-20 ~ +24-20 ~ +24-20 ~ +24-20 ~ +24-20 ~ +24

Additional information

PACi ELITE High Static Pressure Hide Away Inverter+ Single Phase • R410A GAS

, , , , , ,

Reviews

There are no reviews yet.

Be the first to review “PACi ELITE High Static Pressure Hide Away Inverter+ Single Phase • R410A GAS”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.