PACi ELITE High Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS

Compare

From: £2,496.00£3,945.00 ex. VAT

Clear

Description

KIT KIT-71PF1E8D KIT-100PF1E8D KIT-125PF1E8D KIT-140PF1E8D
Remote controller CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B
Cooling capacity Nominal (Min – Max) kW 7.1 (3.2 – 8.0) 10.0 (3.3 – 12.5) 12.5 (3.3 – 14.0) 14.0 (3.3 – 15.5)
UK Cooling capacity Total / Sensible kW 7.9 / 6.0 11.4 / 9.3 12.7 / 9.6 14.1 / 10.3
EER Nominal (Min – Max) W/W 3.84 (5.0 – 3.02) A 4.10 (3.93 – 3.38) A 3.50 (3.93 – 3.04) A 3.25 (3.93 – 2.58) A
SEER W/W 6.00 A+ 5.70 A+ 5.55 5.40
Pdesign kW 7.1 10.0 12.5 14.0
Input power cooling Nominal (Min – Max) kW 1.85 (0.64 – 2.65) 2.44 (0.84 – 3.70) 3.57 (0.84 – 4.60) 4.31 (0.84 – 6.00)
Annual energy consumption (ErP) kWh/a 414 614
Heating capacity Nominal (Min – Max) kW 8.0 (2.8 – 9.0) 11.2 (4.1 – 14.0) 14.0 (4.1 – 16.0) 16.0 (4.1 – 18.0)
UK Heating capacity kW 8.1 14.0 15.9 17.8
Heating capacity at -7°C /-15°C kW — /— — /— — /— 12.32 /—
COP Nominal (Min – Max) W/W 3.85 (4.83 – 3.10) A 4.31 (4.56 – 3.18) A 4.02 (4.56 – 3.08) A 3.60 (4.56 – 3.05) A
SCOP W/W 3.90 A 3.80 A 3.72 3.63
Pdesign at -10°C kW 7.1 10.0 12.5 14.0
Input power heating Nominal (Min – Max) kW 2.08 (0.58 – 2.90) 2.60 (0.90 – 4.40) 3.48 (0.90 – 5.20) 4.44 (0.90 – 5.90)
Annual energy consumption (ErP) kWh/a 2548 3684
Indoor unit S-71PF1E5B S-100PF1E5B S-125PF1E5B S-140PF1E5B
External static pressure Nominal (Min – Max) Pa 70 (10 – 150) 100 (10 – 150) 100 (10 – 150) 100 (10 – 150)
Air volume Hi / Med / Lo m³/min 21 / 19 / 15 32 / 26 / 21 34 / 29 / 23 36 / 32 / 25
Sound pressure Hi / Med / Lo dB(A) 35 / 32 / 26 38 / 34 / 31 39 / 35 / 32 40 / 36 / 33
Dimension H x W x D mm 290 x 1000 x 700 290 x 1400 x 700 290 x 1400 x 700 290 x 1400 x 700
Net weight kg 33 45 45 45
Outdoor unit U-71PE1E8A U-100PE1E8A U-125PE1E8A U-140PE1E8A
Power source V 380 / 400 / 415 380 / 400 / 415 380 / 400 / 415 380 / 400 / 415
Recommended fuse A 16 16 16 16
Connection mm² 2.5 2.5 2.5 2.5
Current Cool A 2.75 / 2.65 / 2.60 3.68 / 3.53 / 3.43 5.52/ 5.29 / 5.12 6.69/ 6.42 / 6.18
Heat A 3.10 / 3.00 / 2.90 3.86/ 3.70 / 3.58 5.44/ 5.26 / 5.05 6.64/ 6.35 / 6.15
Air volume Cool / Heat m³/min 60 / 60 110 / 95 130 / 110 135 / 120
Sound pressure Cool / Heat (Hi) dB(A) 48 / 50 52 / 52 53 / 53 54 / 55
Dimension H x W x D mm 996 x 940 x 340 1416 x 940 x 340 1416 x 940 x 340 1416 x 940 x 340
Net weight kg 71 98 98 98
Piping connections Liquid pipe Inch (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Gas pipe Inch (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)
Pipe length range m 5 ~ 50 5 ~ 75 5 ~ 75 5 ~ 75
Elevation difference (in/out) m 30 30 30 30
Pipe length for additional gas m 30 30 30 30
Additional gas amount g/m 50 50 50 50
Refrigerant (R410A) kg / TCO2 Eq. 2.35 / 4.9068 3.40 / 7.0992 3.40 / 7.0992 3.40 / 7.0992
Operating range Cool Min ~ Max °C -15 ~ +46 -15 ~ +46 -15 ~ +46 -15 ~ +46
Heat Min ~ Max °C -20 ~ +24 -20 ~ +24 -20 ~ +24 -20 ~ +24

Additional information

PACi ELITE High Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS

, , ,

Reviews

There are no reviews yet.

Be the first to review “PACi ELITE High Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.