PACi ELITE High Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS

Compare

From: £2,496.00£3,945.00 ex. VAT

Clear

Description

KITKIT-71PF1E8DKIT-100PF1E8DKIT-125PF1E8DKIT-140PF1E8D
Remote controllerCZ-RTC5BCZ-RTC5BCZ-RTC5BCZ-RTC5B
Cooling capacityNominal (Min – Max)kW7.1 (3.2 – 8.0)10.0 (3.3 – 12.5)12.5 (3.3 – 14.0)14.0 (3.3 – 15.5)
UK Cooling capacityTotal / SensiblekW7.9 / 6.011.4 / 9.312.7 / 9.614.1 / 10.3
EERNominal (Min – Max)W/W3.84 (5.0 – 3.02) A4.10 (3.93 – 3.38) A3.50 (3.93 – 3.04) A3.25 (3.93 – 2.58) A
SEERW/W6.00 A+5.70 A+5.555.40
PdesignkW7.110.012.514.0
Input power coolingNominal (Min – Max)kW1.85 (0.64 – 2.65)2.44 (0.84 – 3.70)3.57 (0.84 – 4.60)4.31 (0.84 – 6.00)
Annual energy consumption (ErP)kWh/a414614
Heating capacityNominal (Min – Max)kW8.0 (2.8 – 9.0)11.2 (4.1 – 14.0)14.0 (4.1 – 16.0)16.0 (4.1 – 18.0)
UK Heating capacitykW8.114.015.917.8
Heating capacity at -7°C /-15°CkW— /—— /—— /—12.32 /—
COPNominal (Min – Max)W/W3.85 (4.83 – 3.10) A4.31 (4.56 – 3.18) A4.02 (4.56 – 3.08) A3.60 (4.56 – 3.05) A
SCOPW/W3.90 A3.80 A3.723.63
Pdesign at -10°CkW7.110.012.514.0
Input power heatingNominal (Min – Max)kW2.08 (0.58 – 2.90)2.60 (0.90 – 4.40)3.48 (0.90 – 5.20)4.44 (0.90 – 5.90)
Annual energy consumption (ErP)kWh/a25483684
Indoor unitS-71PF1E5BS-100PF1E5BS-125PF1E5BS-140PF1E5B
External static pressureNominal (Min – Max)Pa70 (10 – 150)100 (10 – 150)100 (10 – 150)100 (10 – 150)
Air volumeHi / Med / Lom³/min21 / 19 / 1532 / 26 / 2134 / 29 / 2336 / 32 / 25
Sound pressureHi / Med / LodB(A)35 / 32 / 2638 / 34 / 3139 / 35 / 3240 / 36 / 33
DimensionH x W x Dmm290 x 1000 x 700290 x 1400 x 700290 x 1400 x 700290 x 1400 x 700
Net weightkg33454545
Outdoor unitU-71PE1E8AU-100PE1E8AU-125PE1E8AU-140PE1E8A
Power sourceV380 / 400 / 415380 / 400 / 415380 / 400 / 415380 / 400 / 415
Recommended fuseA16161616
Connectionmm²2.52.52.52.5
CurrentCoolA2.75 / 2.65 / 2.603.68 / 3.53 / 3.435.52/ 5.29 / 5.126.69/ 6.42 / 6.18
HeatA3.10 / 3.00 / 2.903.86/ 3.70 / 3.585.44/ 5.26 / 5.056.64/ 6.35 / 6.15
Air volumeCool / Heatm³/min60 / 60110 / 95130 / 110135 / 120
Sound pressureCool / Heat (Hi)dB(A)48 / 5052 / 5253 / 5354 / 55
DimensionH x W x Dmm996 x 940 x 3401416 x 940 x 3401416 x 940 x 3401416 x 940 x 340
Net weightkg71989898
Piping connectionsLiquid pipeInch (mm)3/8 (9.52)3/8 (9.52)3/8 (9.52)3/8 (9.52)
Gas pipeInch (mm)5/8 (15.88)5/8 (15.88)5/8 (15.88)5/8 (15.88)
Pipe length rangem5 ~ 505 ~ 755 ~ 755 ~ 75
Elevation difference (in/out)m30303030
Pipe length for additional gasm30303030
Additional gas amountg/m50505050
Refrigerant (R410A)kg / TCO2 Eq.2.35 / 4.90683.40 / 7.09923.40 / 7.09923.40 / 7.0992
Operating rangeCool Min ~ Max°C-15 ~ +46-15 ~ +46-15 ~ +46-15 ~ +46
Heat Min ~ Max°C-20 ~ +24-20 ~ +24-20 ~ +24-20 ~ +24

Additional information

PACi ELITE High Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS

, , ,

Reviews

There are no reviews yet.

Be the first to review “PACi ELITE High Static Pressure Hide Away Inverter+ 3 Phase • R410A GAS”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.