Sale!

Floor / Ceiling Range

Compare

From: £963.27 - £1,197.00 ex. VAT

Clear

Description

Indoor ABYG18LVTB ABYG24LVTA
Outdoor AOYG18LALL AOYG24LALA
Nominal Capacity (kW) Cooling 5.20 (0.90-5.90) 6.80 (0.90-8.00)
Heating 6.00 (0.90-7.50) 8.00 (0.90-9.10)
UK Total / Sensible Cooling * 4.79 / 3.33 6.05 / 4.51
Power Consumption (kW) Cooling 1.62 2.21
Heating 1.66 2.26
EER / COP (Nominal Conditions) 3.21 / 3.61 3.08 / 3.54
Pdesign (kW) @ -10°C Cooling 5.20 6.80
Heating 5.20 6.00
SEER Cooling 6.10 5.60
SCOP Heating (Average) 4.00 3.90
(QHUJ\ (IÀFLHQF\ &ODVV Cooling A++ A+
Heating (Average) A+ A
Annual Energy Consumption (kWh/a) Cooling 298 425
Heating 1819 2150
Moisture Removal l/h 2.00 2.70
Dimensions (HxWxD) mm Inner 199x990x655 199x990x655
Outer 578x790x300 578x790x315
Net Weight (kg) Inner 27 27
Outer 40 44
Room Air Circulation (high) m3/h Inner 780 980
Outer 2000 2470
Power Supply V-PH-Hz 230 / 1 / 50 230 / 1 / 50
Power Supply To Outdoor Outdoor
Running Current (A) Cooling 7.20 9.70
Heating 7.40 9.90
Starting Current A 7.40 9.90
Suggested MCB/Fuse A 16 16
Interconnecting Cable 3 + E 3 + E
Remote Control Type Wireless Wireless
Sound Pressure (dB(A) Cooling) Indoor Q/L/M/H 31 / 34 / 40 / 43 35 / 40 / 44 / 48
Outdoor H 50 52
Sound Power (dB(A) Cooling) Indoor H 57 61
Outdoor H 62 67
Max Pipe Length m 25 30
Max Height Difference m 15 20
Refrigerant Charge m 15 15
Additional Refrigerant Charge g/m 20 20
Pipe Size (inches) Gas 1/2 5/8
Liquid 1/4 1/4
Operating Range (OC) Cooling -10 ~ 46 -10 ~ 46
Heating -15 ~ 24 -15 ~24
Refrigerant R410A R410A

Additional information

Floor/Ceiling - ABYG-LVTB-LVTA

,

Reviews

There are no reviews yet.

Be the first to review “Floor / Ceiling Range”

Your email address will not be published. Required fields are marked *

Downloads