Indoor unit   FDE100VG FDE125VG FDE140VG
Outdoor unit   FDC100VNA FDC125VNA FDC140VNA
Power source 1 Phase 220-240V, 50Hz / 220V, 60Hz
Nominal cooling capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 )
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 )
Power consumption Cooling/Heating kW 2.85 / 2.90 4.45 / 4.08 5.80 / 4.92
EER/COP Cooling/Heating 3.51 / 3.86 2.81 / 3.43 2.41 / 3.25
Inrush current A 5 5 5
Max. current 24 24 24
Sound power level*1 Indoor Cooling/Heating dB(A) 64 / 64 64 / 64 65 / 65
Outdoor Cooling/Heating 70 / 70 72 / 72 73 / 73
Sound pressure level*1    1 Indoor Cooling (Hi/Me/Lo) 43 / 38 / 34 45 / 40 / 35 45 / 40 / 36
Heating (Hi/Me/Lo) 43 / 38 / 34 45 / 40 / 35 45 / 40 / 36
Outdoor Cooling/Heating 49 / 49 50 / 51 51 / 51
Air flow    1 Indoor Cooling (Hi/Me/Lo) m3/min 26 / 21 / 16.5 29 / 23 / 17 29 / 23 / 18
Heating (Hi/Me/Lo) 26 / 21 / 16.5 29 / 23 / 17 29 / 23 / 18
Outdoor Cooling/Heating 75 / 73 75 / 73 75 / 73
Exterior dimensions Indoor HeightxWidthxDepth mm 250 x 1,620 x 690
Outdoor 845 x 970 x 370
Net weight Indoor kg 43
Outdoor 81
Ref.piping size Liquid/Gas ømm 9.52(3/8″) / 15.88(5/8″)
Refrigerant line (one way) length m Max.50
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operating temperature range Cooling °C -15~43*3
Heating -20~20
Air filter, Q’ty Pocket Plastic net x2(Washable)
Remote control (option) wired:RC-EX3, RC-E5, RCH-E3  wireless:RCN-E-E2