DVM-S – 3pipe Heat Recovery HP 8 to 12

From: £5,245.00£7,074.00 ex. VAT

Clear

Note: All systems must be installed by Certified Installer.

Description

TypeDVM SDVM SDVM S
Model NameAM080JXVHGR/ETAM100JXVHGR/ETAM120JXVHGR/ET
Power SupplyØ, #, V, Hz3, 4, 380-415, 503, 4, 380-415, 503, 4, 380-415, 50
ModeHEAT RECOVERYHEAT RECOVERYHEAT RECOVERY
PerformanceHPHP81012
CapacityCoolingkW22.4 / 22.428.0 / 28.033.6 / 33.6
HeatingkW25.2 / 22.431.5 / 28.037.8 / 33.6
Maximum number of connectable indoor unitsEA141821
Total capacity of the connected Indoor UnitsMin.kW11.214.016.8
Total capacity of the connected Indoor UnitsMax.kW29.136.443.7
PowerPower InputCoolingkW4.59 / 4.596.22 / 6.227.57 / 7.57
HeatingkW4.59 / 4.085.89 / 5.237.56 / 6.72
Current InputCoolingA7.4010.0012.10
HeatingA7.409.4012.10
CurrentMinimum SscMVA3.14.55.3
MCAA18.021.125.0
MFAA253232
EfficiencyEERCoolingW/W4.88 / 4.884.50 / 4.504.44 / 4.44
COPHeatingW/W5.49 / 5.495.35 / 5.355.00 / 5.00
ESEERW/W8.007.437.23
CasingMaterialBodyEGI Steel PlateEGI Steel PlateEGI Steel Plate
BaseEGI Steel PlateEGI Steel PlateEGI Steel Plate
Heat ExchangerTypeFin & TubeFin & TubeFin & Tube
MaterialFinAlAlAl
TubeCuCuCu
Fin TreatmentAnti-corrosionAnti-corrosionAnti-corrosion
CompressorOutputkW x n5.18 x 16.39 x 16.39 x 1
Model NameDS-GB052FAV* x 1DS-GB066FAV* x 1DS-GB066FAV* x 1
OilTypePVEPVEPVE
Initial chargecc x n1,100 x 11,100 x 11,100 x 1
FanTypePropellerPropellerPropeller
Discharge directionTopTopTop
QuantityEA111
Air Flow Ratem3/min170170200
l/s2,8332,8333,333
External Static PressureMax.mmAq888
Pa78.4578.4578.45
Fan MotorTypeBLDC MotorBLDC MotorBLDC Motor
OutputW x n830 x 1830 x 1830 x 1
Piping ConnectionsLiquid PipeTypeBraze connectionBraze connectionBraze connection
Φ, mm (inch)9.52 (3/8)9.52 (3/8)12.70 (1/2)
Gas PipeTypeBraze connectionBraze connectionBraze connection
Φ, mm (inch)19.05 (3/4)22.22 (7/8)28.58 (1-1/8)
High pressure Gas Pipe(HR Only)TypeBraze connectionBraze connectionBraze connection
Φ, mm (inch)15.88 (5/8)19.05 (3/4)19.05 (3/4)
Heat InsulationAll liquid and gas pipesAll liquid and gas pipesAll liquid and gas pipes
Piping length (ODU-IDU)Max. [Equiv.]m200[220]200[220]200[220]
Piping length (1st Branch-IDU)Max.m909090
Total piping length (System)Max.m1,0001,0001,000
Level difference (ODU in highest position)Max.m110110110
Level difference (IDU in highest position)Max.m110110110
Level difference (IDU-IDU)Max.m404040
Wiring connectionsTransmission Cablemm20.750.750.75
RemarkF1, F2F1, F2F1, F2
Power supply intakeBoth indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
RefrigerantTypeR410AR410AR410A
Factory Chargingkg6.56.56.5
tCO2e13.5813.5813.58
SoundSound PressureCoolingdB(A)575862
HeatingdB(A)596064
Sound PowerdB(A)777981
External DimensionNet Weightkg200.5200.5200.5
Shipping Weightkg216.5216.5216.5
Net Dimensions (WxHxD)mm880 x 1,695 x 765880 x 1,695 x 765880 x 1,695 x 765
Shipping Dimensions (WxHxD)mm948 x 1,887 x 832948 x 1,887 x 832948 x 1,887 x 832
Operating Temp. RangeCooling-15 ~ 48-15 ~ 48-15 ~ 48
Heating-25 ~ 24-25 ~ 24-25 ~ 24

Additional information

DVM-S - 3pipe Heat Recovery HP 8 to 12

AM080JXVHGR/ET, AM100JXVHGR/ET, AM120JXVHGR/ET

Reviews

There are no reviews yet.

Be the first to review “DVM-S – 3pipe Heat Recovery HP 8 to 12”

Your email address will not be published. Required fields are marked *

Downloads