Ducted Split Systems – Seasonal Smart R410A

From: £2,433.00£3,832.00 ex. VAT


Note: All systems must be installed by Certified Installer.

Description

Indoor Units Single Phase 3 Phase
FBA71A9 FBA100A FBA125A FBA140A FBA71A9 FBA100A FBA125A FBA140A
Capacity UK Total Cooling kW 7.76 10.80 13.60 14.90 7.76 10.80 13.60 14.90
UK Sensible Cooling kW 5.32 7.44 9.30 10.25 5.32 7.44 9.30 10.25
Nominal Cooling kW 6.8 9.5 12.0 13.4 6.8 9.5 12.0 13.4
Nominal Heating kW 7.5 10.8 13.5 15.5 7.5 10.8 13.5 15.5
Seasonal Efficiency (EN14825) COOLING Energy Label A++ A+ A++ A++ A+ A++
Pdesign kW 6.8 9.5 12.0 6.8 9.5 12.0
SEER 6.16 5.87 6.11 6.16 5.87 6.11
Annual Energy Consumption kWh 386 566 687 386 566 687
Seasonal Efficiency (EN14825) HEATING Energy Label A+ A++ A+ A+ A++ A+
Pdesign kW 6.0 11.3 12.7 6.0 11.3 12.7
SCOP 4.31 4.78 4.28 4.31 4.78 4.28
Annual Energy Consumption kWh 1949 3310 4154 1949 3310 4154
Nominal Efficiency EER / COP 3.60 / 4.01 3.81 / 4.41 3.31 / 3.90 3.35 / 3.60 3.60 / 4.01 3.81 / 4.41 3.31 / 3.90 3.35 / 3.60
Air Flow Rate (Cooling) High / Nom / Low m3/sec 0.300 / 0.250 /
0.208
0.483 / 0.433 /
0.383
0.567 / 0.483 /
0.392
0.567 / 0.483 /
0.393
0.300 / 0.250 /
0.208
0.483 / 0.433 /
0.383
0.567 / 0.483 /
0.392
0.567 / 0.483 /
0.393
External Static Pressure High / Nom Pa 150 / 30 150 / 40 150 / 50 150 / 30 150 / 40 150 / 50
Dimensions Height mm 245 245 245 245 245 245 245 245
Width mm 1000 1400 1400 1400 1000 1400 1400 1400
Depth mm 800 800 800 800 800 800 800 800
Weight kg 35 46 35 46
Sound Pressure (Cooling) High / Nom / Low dBA 30 / 28 / 25 34 / 32 / 30 37 / 35 / 32 37 / 35 / 32 30 / 28 / 25 34 / 32 / 30 37 / 35 / 32 37 / 35 / 32
Sound Pressure (Heating) High / Nom / Low dBA 31 / 28 / 25 36 / 33 / 30 38 / 35 / 32 38 / 35 / 32 31 / 28 / 25 36 / 33 / 30 38 / 35 / 32 38 / 35 / 32
Sound Power (Cooling) dBA 56 58 62 62 56 58 62 62
Outdoor Units RZQG71L9V1 RZQG100L9V1 RZQG125L9V1 RZQG140L9V1 RZQG71L8Y1 RZQG100L8Y1 RZQG125L8Y1 RZQG140LY1
Dimensions Height x Width x Depth mm 990 x 940 x 320 1430 x 940 x 320 990 x 940 x 320 1430 x 940 x 320
Weight kg 69 95 95 95 80 101 101 101
Electrical Details Power Supply 1ph 3ph
Running Current A 7.93 9.97 12.87 16.43 2.98 3.75 4.84 6.18
Starting Current A 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
Max Fuse Size A 20 32 32 32 16 20 20 20
Interconnection Wiring Core / Cable size 3+E / 1.5 3+E / 1.5
Piping Connections Liquid / Gas inches (mm) 3/8 ( 9.5) / 5/8 (15.9) 3/8 ( 9.5) / 5/8 (15.9)
Pipework Maximum Length m 50 75 75 75 50 75 75 75
Maximum Vertical Rise m 30 30 30 30 30 30 30 30
Precharged to m 30 30 30 30 30 30 30 30
Additional Charge g/m Refer to Installation Manual Refer to Installation Manual
Holding Charge kg 2.90 4.00 4.00 4.00 2.90 4.00 4.00 4.00
Sound Pressure (Cooling) Nom / Night Quiet dBA 48 / 43 50 / 45 51 / 45 52 / 45 48 / 43 50 / 45 51 / 45 52 / 45
Sound Pressure (Heating) Nom / Night Quiet dBA 50 / 43 52 / 45 53 / 45 53 / 45 50 / 43 52 / 45 53 / 45 53 / 45
Sound Power (Cooling) dBA 64 66 67 69 64 66 67 69
Operating Range (Cooling) Min / Max °CDB -15 / 50 -15 / 50 -15 / 50 -15 / 50 -15 / 50 -15 / 50 -15 / 50 -15 / 50
Operating Range (Heating) Min / Max °CWB -20 / 15.5 -20 / 15.5 -20 / 15.5 -20 / 15.5 -20 / 15.5 -20 / 15.5 -20 / 15.5 -20 / 15.5
Air Flow Rate (Cooling) High m3/sec 0.983 1.166 1.166 1.400 0.983 1.166 1.166 1.400

Additional information

DAIKIN Ducted – Seasonal Smart - R410A

, , , , , , ,

Reviews

There are no reviews yet.

Be the first to review “Ducted Split Systems – Seasonal Smart R410A”

Downloads

No files uploaded.