Ducted Split Systems – Seasonal Smart R410A

From: £2,433.00£3,832.00


Note: All systems must be installed by Certified Installer.

Description

Indoor UnitsSingle Phase3 Phase
FBA71A9FBA100AFBA125AFBA140AFBA71A9FBA100AFBA125AFBA140A
CapacityUK Total CoolingkW7.7610.8013.6014.907.7610.8013.6014.90
UK Sensible CoolingkW5.327.449.3010.255.327.449.3010.25
Nominal CoolingkW6.89.512.013.46.89.512.013.4
Nominal HeatingkW7.510.813.515.57.510.813.515.5
Seasonal Efficiency (EN14825) COOLINGEnergy LabelA++A+A++A++A+A++
PdesignkW6.89.512.06.89.512.0
SEER6.165.876.116.165.876.11
Annual Energy ConsumptionkWh386566687386566687
Seasonal Efficiency (EN14825) HEATINGEnergy LabelA+A++A+A+A++A+
PdesignkW6.011.312.76.011.312.7
SCOP4.314.784.284.314.784.28
Annual Energy ConsumptionkWh194933104154194933104154
Nominal EfficiencyEER / COP3.60 / 4.013.81 / 4.413.31 / 3.903.35 / 3.603.60 / 4.013.81 / 4.413.31 / 3.903.35 / 3.60
Air Flow Rate (Cooling)High / Nom / Lowm3/sec0.300 / 0.250 /
0.208
0.483 / 0.433 /
0.383
0.567 / 0.483 /
0.392
0.567 / 0.483 /
0.393
0.300 / 0.250 /
0.208
0.483 / 0.433 /
0.383
0.567 / 0.483 /
0.392
0.567 / 0.483 /
0.393
External Static PressureHigh / NomPa150 / 30150 / 40150 / 50150 / 30150 / 40150 / 50
DimensionsHeightmm245245245245245245245245
Widthmm10001400140014001000140014001400
Depthmm800800800800800800800800
Weightkg35463546
Sound Pressure (Cooling)High / Nom / LowdBA30 / 28 / 2534 / 32 / 3037 / 35 / 3237 / 35 / 3230 / 28 / 2534 / 32 / 3037 / 35 / 3237 / 35 / 32
Sound Pressure (Heating)High / Nom / LowdBA31 / 28 / 2536 / 33 / 3038 / 35 / 3238 / 35 / 3231 / 28 / 2536 / 33 / 3038 / 35 / 3238 / 35 / 32
Sound Power (Cooling)dBA5658626256586262
Outdoor UnitsRZQG71L9V1RZQG100L9V1RZQG125L9V1RZQG140L9V1RZQG71L8Y1RZQG100L8Y1RZQG125L8Y1RZQG140LY1
DimensionsHeight x Width x Depthmm990 x 940 x 3201430 x 940 x 320990 x 940 x 3201430 x 940 x 320
Weightkg6995959580101101101
Electrical DetailsPower Supply1ph3ph
Running CurrentA7.939.9712.8716.432.983.754.846.18
Starting CurrentA4.04.04.04.04.04.04.04.0
Max Fuse SizeA2032323216202020
Interconnection WiringCore / Cable size3+E / 1.53+E / 1.5
Piping ConnectionsLiquid / Gasinches (mm)3/8 ( 9.5) / 5/8 (15.9)3/8 ( 9.5) / 5/8 (15.9)
PipeworkMaximum Lengthm5075757550757575
Maximum Vertical Risem3030303030303030
Precharged tom3030303030303030
Additional Chargeg/mRefer to Installation ManualRefer to Installation Manual
Holding Chargekg2.904.004.004.002.904.004.004.00
Sound Pressure (Cooling)Nom / Night QuietdBA48 / 4350 / 4551 / 4552 / 4548 / 4350 / 4551 / 4552 / 45
Sound Pressure (Heating)Nom / Night QuietdBA50 / 4352 / 4553 / 4553 / 4550 / 4352 / 4553 / 4553 / 45
Sound Power (Cooling)dBA6466676964666769
Operating Range (Cooling)Min / Max°CDB-15 / 50-15 / 50-15 / 50-15 / 50-15 / 50-15 / 50-15 / 50-15 / 50
Operating Range (Heating)Min / Max°CWB-20 / 15.5-20 / 15.5-20 / 15.5-20 / 15.5-20 / 15.5-20 / 15.5-20 / 15.5-20 / 15.5
Air Flow Rate (Cooling)Highm3/sec0.9831.1661.1661.4000.9831.1661.1661.400

Additional information

DAIKIN Ducted – Seasonal Smart - R410A

, , , , , , ,

Reviews

There are no reviews yet.

Be the first to review “Ducted Split Systems – Seasonal Smart R410A”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.