Indoor Units Vertical Ducted
FNA25A FNA35A FNA50A FNA60A
Capacity UK Total Cooling kW 2.54 3.32 4.89 5.86
UK Sensible Cooling kW 1.89 2.26 3.66 4.11
Nominal Cooling kW 2.4 3.4 5.0 6.0
Nominal Heating kW 3.2 4.0 5.8 7.0
Seasonal Efficiency (EN14825 COOLING Energy Label A+ A+ A+ A
Pdesign kW 2.6 3.4 5.0 6.0
SEER 5.63 5.65 5.72 5.51
Annual Energy Consumption kWh 162 211 306 381
Seasonal Efficiency (EN14825) HEATING Energy Label A+ A+ A+ A+
Pdesign kW 2.8 2.9 4.0 4.6
SCOP 4.24 4.05 4.09 4.16
Annual Energy Consumption kWh 925 1002 1369 1548
Nominal Efficiency EER / COP 3.77 / 4.00 3.06 / 3.48 3.35 / 3.34 2.68 / 3.11
Air Flow Rate (Cooling) High / Nom / Low m3/sec 0.145 / 0.133 / 0.122 0.145 / 0.133 / 0.122 0.267 / 0.247 / 0.225 0.225 / 0.247 / 0.025
External Static Pressure High / Nominal Pa 48 / 30 49 / 40
Dimensions Height (with legs) mm 620 (720) 620 (720)
Width mm 750 1150
Depth mm 200 200
Weight kg 23 30
Sound Pressure (Cooling) High / Nom / Low dBA 33 / 31 / 28 33 / 31 / 28 36 / 33 / 30 36 / 33 / 30
Sound Pressure (Heating) High / Nom / Low dBA 33 / 31 / 28 33 / 31 / 28 36 / 33 / 30 36 / 33 / 30
Sound Power dBA 53 56
Outdoor Units RXS25L3 RXS35L3 RXS50L RXS60L
Dimensions Height x Width x Depth mm 550 x 765 x 285 550 x 765 x 285 735 x 825 x 300 735 x 825 x 300
Weight kg 34 34 47 48
Electrical Details Power Supply 1ph
Running Current A 2.90 4.70 6.30 9.40
Starting Current A 3.3 4.3 6.8 10.2
Max Fuse Size A 16 16 20 20
Interconnection Wiring Core / Cable size 3+E / 1.5 3+E / 1.5
Piping Connections Liquid / Gas inches (mm) 1/4 (6.4) / 3/8 (9.5) 1/4 (6.4) / 1/2 (12.7)
Pipework Maximum Length m 20 20 30 30
Maximum Vertical Rise m 15 15 20 20
Precharged to m 10 10 10 10
Additional Charge g/m 20
Holding Charge kg 1.00 1.20 1.70 1.50
Sound Pressure (Cooling) High / Silent Operation dBA 46 / 43 48 / 44 48 / 44 49 / 46
Sound Pressure (Heating) High / Silent Operation dBA 48 / 45 48 / 45 48 / – 48 / –
Sound Power (Cooling) dBA 59 61 61 62
Operating Range (Cooling) Min / Max °CDB -10 / 46 -10 / 46 -10 / 46 -10 / 46
Operating Range (Heating) Min / Max °CWB -15 / 18 -15 / 18 -15 / 18 -15 / 18
Air Flow Rate (Cooling) High m3/sec 0.558 0.600 0.848 0.836