Description

Indoor Units FFA25A FFA35A FFA50A FFA60A
Capacity UK Total Cooling kW 2.44 3.32 4.62 5.72
UK Sensible Cooling kW 1.81 2.28 3.40 4.20
Nominal Cooling kW 2.5 3.4 4.7 5.8
Nominal Heating kW 3.2 4.0 5.5 7.0
Seasonal Efficiency (EN14825) COOLING Energy Label A++ A++ A+ A+
Pdesign kW 2.5 3.4 5.0 5.7
SEER 6.11 6.32 5.93 5.71
Annual Energy Consumption kWh 143 188 295 349
Seasonal Efficiency (EN14825) HEATING Energy Label A+ A+ A A+
Pdesign kW 2.31 3.10 3.84 3.96
SCOP 4.24 4.10 3.90 4.04
Annual Energy Consumption kWh 763 1059 1378 1373
Nominal Efficiency EER/COP 4.53 / 3.90 3.78 / 3.50 3.21 / 3.49 3.02 / 3.41
Air Flow Rate (Cooling) High / Nom / Low m3/sec 0.150 / 0.133 / 0.108 0.167 / 0.142 / 0.108 0.200 / 0.167 / 0.125 0.242 / 0.208 / 0.158
Dimensions
(with Decoration Panel)
Height mm 260 (306) 260 (306) 260 (306) 260 (306)
Width mm 575 (620) 575 (620) 575 (620) 575 (620)
Depth mm 575 (620) 575 (620) 575 (620) 575 (620)
Weight (with Decoration Panel)                                      kg kg 16 (18.8) 16 (18.8) 17.5 (20.2) 17.5 (20.2)
Sound Pressure (Cooling) High / Nom / Low dBA 31 / 28.5 / 25 34 / 30.5 / 25 39 / 34 / 27 43 / 40 / 32
Sound Pressure (Heating) High / Nom / Low dBA 31 / 28.5 / 25 34 / 30.5 / 25 39 / 34 / 27 43 / 40 / 32
Sound Power dBA 48 51 56 60
Outdoor Units RXS25L3 RXS35L3 RXS50L RXS60L
Dimensions Height x Width x Depth mm 550 x 765 x 285 550 x 765 x 285 735 x 825 x 300 735 x 825 x 300
Weight kg 34 34 47 48
Electrical Details Power Supply 1ph
Running Current                   A A 4.00 4.00 6.90 8.30
Starting Current A 3.3 4.3 6.8 10.2
Max Fuse Size A 10 10 20 20
Interconnection Wiring Core / Cable size 3+E / 1.5 3+E / 1.5
Piping Connections Liquid / Gas inches (mm) 1/4 (6.4) / 3/8 (9.5) 1/4 (6.4) / 1/2 (12.7)
Pipework Maximum Length m 20 20 30 30
Maximum Vertical Rise m 15 15 20 20
Precharged to m 10 10 10 10
Additional Charge g/m 20
Holding Charge kg 1.00 1.20 1.70 1.50
Sound Pressure (Cooling) High / Silent Operation dBA 46 / 43 48 / 44 48 / 44 49 / 46
Sound Pressure (Heating) High / Silent Operation dBA 48 / 45 48 / 45 48 / – 48 / –
Sound Power (Cooling) dBA 61 61 62 62
Operating Range (Cooling) Min / Max °CDB -10 / 46 -10 / 46 -10 / 46 -10 / 46
Operating Range (Heating) Min / Max °CWB -15 / 18 -15 / 18 -15 / 18 -15 / 18
Air Flow Rate (Cooling) High m3/sec 0.588 0.600 0.848 0.836