Ceiling Suspended Split Systems (3Phase) R410A

  • Full Systems (Indoor + Outdoor Units + Remote Controller)

From: £2,121.00£3,122.00 ex. VAT


Note: All systems must be installed by Certified Installer.

Description

INDOOR UV36 NK2 UV42 NL2 UV48 NL2 UV60 NL2
Capacity Cooling Min / Nom / Max kW 3.8 / 9.5 / 10.5 5.0 / 12.5 / 13.8 5.3 / 13.3 / 14.6 5.7 / 14.4 / 15.7
Heating Min / Nom / Max kW 4.2 / 10.5 / 11.6 5.6 / 13.6 / 15.4 6.4 / 15.3 / 17.6 6.8 / 16.8 / 18.7
Low Temperature Capacity Heating -7°C Max kW 9,4 12,5 14,3 15,2
Power Input (Set) Cooling Nom kW 2,78 3,89 4,28 5,24
Heating Nom kW 3,08 3,68 4,49 5,42
Power Input (Indoor) Nom W 90 130 140 150
Running Current Cooling / Heating Nom A 4.0 / 4.4 5.6 / 5.3 6.2 / 6.5 7.6 / 7.9
Power Supply Ø / V / Hz 1 / 220-240 / 50 1 / 220-240 / 50 1 / 220-240 / 50 1 / 220-240 / 50
EER 3,42 3,21 3,11 2,75
COP 3,41 3,70 3,41 3,10
SEER 5,11
SCOP 3,81
Pdesign (@ -10°C) kW 7,6
Seasonal Energy Label Cooling / Heating A / A
Annual Energy Consumption Cooling / Heating kWh 652 / 2,800
Piping Connection Liquid mm Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Gas mm Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8)
Drain O.D. / I.D. mm 21.5 / 16.0 21.5 / 16.0 21.5 / 16.0 21.5 / 16.0
Air Flow Rate High / Medium / Low m³/min 21.4 / 19.8 / 18.2 28.6 / 26.9 / 25.2 30.0 / 28.3 / 26.6 31.5 / 29.7 / 28.0
Sound Pressure Cooling High / Medium / Low dBA 45 / 44 / 41 46 / 44 / 43 47 / 46 / 44 48 / 47 / 45
Sound Power Cooling Max dBA 63 63 63 63
Dehumidification Rate l/h 3,5 4,5 5,8 6,2
Dimensions Body W x H x D mm 1,350 x 650 x 220 1,750 x 650 x 220 1,750 x 650 x 220 1,750 x 650 x 220
Net Weight Body kg 34,1 42,5 42,5 42,5

 

OUTDOOR UU37W UO2 UU43W U32 UU49W U32 UU61W U32
Compressor Type Twin Rotary Twin Rotary Twin Rotary Twin Rotary
Airflow Rate Nom m³/min 90 110 110 110
Sound Pressure Cooling Nom dBA 53 52 52 52
Heating Nom dBA 54 54 54 54
Sound Power Cooling Max dBA 66 67 68 71
Dimensions W x H x D mm 950 x 1,170 x 330 950 x 1,380 x 330 950 x 1,380 x 330 950 x 1,380 x 330
Net Weight kg 85,0 96,0 96,0 96,0
Refrigerant Type R410A R410A R410A R410A
Charge g 2 800 3 400 3 400 3 400
Additional Charge g/m 40 40 40 40
GWP 2087,5 2087,5 2087,5 2087,5
TCO2eq 5,8 7,1 7,1 7,1
Operation Range (Outdoor) Cooling Min ~ Max °C DB -15 ~ 48 -15 ~ 48 -15 ~ 48 -15 ~ 48
Heating Min ~ Max °C WB -18 ~ 18 -18 ~ 18 -18 ~ 18 -18 ~ 18
Power Supply Ø / V / Hz 3 / 380-415 / 50 3 / 380-415 / 50 3 / 380-415 / 50 3 / 380-415 / 50
Power Supply Cable No. x mm² 5C x 2.5 5C x 2.5 5C x 2.5 5C x 2.5
Transmission Cable No. x mm² 4C x 0.75 4Cx 0.75 4C x 0.75 4C x 0.75
Maximum Running Current A 11,0 12,5 13,5 14,6
Maximum Circuit Breaker Rating A 20 20 20 20
Piping Length Total Min ~ Max m 5 ~ 50 5 ~ 75 5 ~ 75 5 ~ 75
Piping Elevation Difference IDU – ODU Max m 30 30 30 30
Piping Connection Liquid mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Gas mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8)

Additional information

CEILING SUSPENDED (3Phase)

, , ,

Reviews

There are no reviews yet.

Be the first to review “Ceiling Suspended Split Systems (3Phase) R410A”

Downloads

No files uploaded.