Sale!

Ceiling Suspended Range – 1 Phase

Compare

From: £1,547.91 - £2,091.60 ex. VAT

Clear

Description

IndoorABYG30LRTEABYG36LRTEABYG45LRTA
OutdoorAOYG30LETLAOYG36LETLAOYG45LETL
Nominal Capacity (kW)Cooling8.50 (2.80-10.00)9.40 (2.80-11.20)12.10 (4.00-13.30)
Heating10.00 (2.70-11.20)11.20 (2.70-12.70)13.30 (4.20-15.50)
UK Total / Sensible Cooling *8.53 / 6.208.90 / 6.4711.24 / 8.43
Power Consumption (kW)Cooling2.652.933.77
Heating2.773.023.68
EER / COP (Nominal Conditions)3.21 / 3.613.21 / 3.713.21 / 3.61
Pdesign (kW) @ -10°CCooling8.509.40
Heating8.008.70
SEERCooling6.106.00
SCOPHeating (Average)4.204.10
(QHUJ\ (IÀFLHQF\ &ODVVCoolingA++A+
Heating (Average)A+A+
Annual Energy Consumption (kWh/a)Cooling487548
Heating26622965
Moisture Removall/h2.503.004.00
Dimensions (HxWxD) mmInner240x1660x700240x1660x700240x1660x700
Outer830x900x330830x900x3301290x900x330
Net Weight (kg)Inner464646
Outer616186
Room Air Circulation (high) m3/hInner166019002100
Outer360038006200
Power SupplyV-PH-Hz230 / 1 / 50230 / 1 / 50230 / 1 / 50
Power Supply ToOutdoorOutdoorOutdoor
Running Current (A)Cooling11.6012.8016.50
Heating12.2013.2016.10
Starting CurrentA12.2013.7022.50
Suggested MCB/FuseA202525
Interconnecting Cable3 + E3 + E3 + E
Remote Control TypeWirelessWirelessWireless
Sound Pressure (dB(A) Cooling)Indoor Q/L/M/H32 / 37 / 43 / 4532 / 37 / 43 / 4734 / 39 /45 / 49
Outdoor H535455
Sound Power (dB(A) Cooling)Indoor H5760
Outdoor H6869
Max Pipe Lengthm505050
Max Height Differencem303030
Refrigerant Chargem202020
Additional Refrigerant Chargeg/m404040
Pipe Size (inches)Gas3/83/83/8
Liquid5/85/85/8
Operating Range (OC)Cooling-15 ~ 46-15 ~ 46-15 ~ 46
Heating-15 ~ 24-15 ~ 24-15 ~ 24
RefrigerantR410AR410AR410A

Additional information

Ceiling Suspended - ABYG-LRTE-LRTA Single Phase

, ,

Reviews

There are no reviews yet.

Be the first to review “Ceiling Suspended Range – 1 Phase”

Your email address will not be published. Required fields are marked *

Downloads