Indoor UnitAC100RN4PKG/EUAC120RN4PKG/EUAC140RN4PKG/EU
Outdoor Unit-AC100RXADNG/EUAC120RXADNG/EUAC140RXADNG/EU
CapacityCooling (Min/Nominal/Max)kW3.0 / 10.0 / 12.03.5 / 12.0 / 13.53.5 / 13.4 / 15.5
Heating up to +7°C (Min/Nominal/Max)kW2.2 / 11.2 / 15.53.5 / 13.2 / 15.53.5 / 15.5 / 18.0
Heating @ -5°CkW11,0012.915.2
Heating @ -15°CkW9.711.513.5
Energy Efficiency CoolingSEERW/W6.8 / A++6.0 / A+6.4
ConsumptionkWh/a515TBD
PdesignckW10,0TBD
EERW/W3.082.692.81
Energy Efficiency HeatingSCOPW/W4.3 / A+4.0 / A+4.1
ConsumptionkWh/a1726TBD
Pdesignh (average)kW5.36.58.4
COPW/W3.53.263.35
AirFlow RateIndoor Unit (High/Mid/Low)m3/min72.072.0110.0
Sound PowerIndoor UnitdB(A)616161
Outdoor UnitdB(A)697069
Sound PressureIndoor Unit (Silent/Low/Mid/High)dB(A)33 / 39 / 4435 / 40 / 4537 / 41 / 45
Outdoor UnitdB(A)52 / 5454 / 5653 / 54
Fan/ Outdoor unitTypeTurboTurboTurbo
PowerW979797
NumberEA111
Operating Temp. RangeCooling°C-15 ~ 50-15 ~ 50-15 ~ 50
Heating°C-20 ~ 24-20 ~ 24-20 ~ 24
Power SourceIndoor UnitV / Hz / Φ/ #220~240/ 50/ 1/ 2220~240/ 50/ 1/ 2220~240/ 50/ 1/ 2
Outdoor Unit 1PV / Hz / Φ/ #220~240/ 50/ 1/ 2220~240/ 50/ 1/ 2220~240/ 50/ 1/ 2
Outdoor Unit 3PV / Hz / Φ/ #380~415/ 50/ 3/ 4380~415/ 50/ 3/ 4380~415/ 50/ 3/ 4
Compressor TypeOutdoor UnitTypeTwin BLDCTwin BLDCTwin BLDC
Power (Min/ Nominal/Max)CoolingkW0.60 / 3.24 / 4.700.90 / 4.45 / 5.300.80 / 4.76 / 6.45
HeatingkW0.46 / 3.20 / 5.400.75 / 4.05 / 5.600.70 / 4.62 / 7.36
Current InputCooling (Min/Std/Max)A3.0 / 14.4 / 20.40.75 / 4.05 / 5.603.7 / 20.6 / 28.0
Heating (Min/Std/Max)A3.0 / 14.4 / 20.43.7 / 17.7 / 26.03.7 / 20.6 / 28.0
Cooling- Tri-Phase (Min/Std/Max)A1.5 / 5.1 / 7.12.1 / 6.9 / 10.02.1 / 7.3 / 10.5
Heating- Tri-Phase (Min/Std/Max)A1.2 / 5.0 / 8.42.1 / 6.3 / 12.01.9 / 7.1 / 12.0
Net Dimensions (W x H x D)Indoor Unitmm947 x 365 x 947947 x 365 x 947947 x 365 x 947
Outdoor Unitmm940 x 998 x 330940 x 998 x 330940 x 1210 x 330
Net WeightIndoor Unitkg23.523.525.5
Outdoor Unitkg75,081,091.5
RefrigerantTypeR32(Contains fluorinated greenhouse gases. GWP=675)
Factory chargingkg2.7 / 30m2.7 / 30m2.9 / 30m
Charging Ton equivalent CO2tCO2e1.82 tCO2e1.82 tCO2e1.96 tCO2e
Additional refrigerant chargingg / m505050
Piping ConnectionsLiquid PipeΦ.inch3 / 83 / 83 / 8
Gas PipeΦ.inch5 / 85 / 85 / 8
Piping LengthMin/ Maxm505075
Piping HeightMaxm303030
Piping ConnectionsDrain pipeΦ.mmVP25 (OD32.ID25)VP25 (OD32.ID25)VP25 (OD32.ID25)
PanelModel codePC4NUNMANPC4NUNMANPC4NUNMAN
Net Dimensions (W x H x D)mm1050 x 66 x 10501050 x 66 x 10501050 x 66 x 1050
Net Weightkg2.72.72.7
AccessoiresDrain pumpincludedincludedincluded
Max lifting height/ displacementmm / l/h750/24750/24750/24

Additional information

360 Cassette split system (3 Phase) R32

Up to 100 sq.m. room – AC100RN4PKG/EU AC100RXADNG/EU, Up to 120 sq.m. room – AC120RN4PKG/EU AC120RXADNG/EU, Up to 135 sq.m. room – AC140RN4PKG/EU AC140RXADNG/EU

Reviews

There are no reviews yet.

Be the first to review “360 Cassette split system (3 Phase) R32”

Your email address will not be published. Required fields are marked *

Downloads

No files uploaded.