Sale!

3-Pipe Heat Recovery (HP 18 to 26)

£8,802.50 - £14,217.70 ex. VAT

Clear

Note: All systems must be installed by Certified Installer.

Description

CombinationMMY-AP2216FT8P-UKAP2416FT8P-UKAP2616FT8P-UK
Model Name Heat RecoveryMMY-MAP1806FT8P-UKMAP2006FT8P-UKMAP1206FT8P-UK MAP1006FT8P-UKMAP1406FT8P-UK MAP1006FT8P-UKMAP1406FT8P-UK MAP1206FT8P-UK
Capacity Rangehp1820222426
Maximum Number of Indoor UnitsQTY4041495458
Cooling CapacitykW50.456.061.568.073.5
Heating CapacitykW56.558.069.076.582.5
Operating Range Cooling/Heating°C-10.0 to 46.0/
-25.0 to 15.5
-10.0 to 46.0/
-25.0 to 15.5
-10.0 to 46.0/
-25.0 to 15.5
-10.0 to 46.0/
-25.0 to 15.5
-10.0 to 46.0/
-25.0 to 15.5
CoolingPower ConsumptionkW16.0018.6017.7120.6622.45
EER/SEER/Energy Efficiency Class (or ηsc %)3.15/5.94/234.63.01/5.68/224.23.47/6.07/239.83.29/5.88/232.23.27/5.84/230.6
HeatingPower ConsumptionkW13.7015.9015.7517.5519.20
COP/SCOP/Energy Efficiency Class (or ηsc(A) %)3.67/3.59/140.63.52/3.60/141.03.90/3.64/142.63.87/3.56/139.43.83/3.64/142.6
Fan(s)Standard Air Flow Hl/s480649723389 + 26943389 + 26943389 + 3389
Standard Air Flow Hm3/h173001790012200 + 970012200 + 970012200 + 12200
External Static PressurePa4040504040
SoundPressure Level C/HdB(A)61/6261/6263/6564/6664.5/66.5
Power Level C/HdB(A)83/8483/8483.5/85.584/8684/86
Unit(s)Height x Width x Depthmm1830 x 1600 x 7801830 x 1600 x 7801830 x 2220 x 7801830 x 2220 x 7801830 x 2440 x 780
Weightkg377377316 + 263316 + 263316 + 316
Refrigerant Base Chargekg111111 + 1111 + 1111 + 11
Pipe ConnectionsSuction Gas Pipe Brazinginch1-1/81-1/81-3/81-3/81-3/8
Discharge Pipe Brazinginch7/87/81-1/81-1/81-1/8
Liquid Pipe Flareinch3/43/43/43/47/8
Balance Pipe Flareinch3/83/83/83/83/8
MaximumEquivalent Lengthm200200200200200
Real Lengthm180180180180180
Total Pipe Length (Liquid Line Real Length)m300300300300300
Length To First Branch Height Difference Between Indoor Units ≤ 3 mm100100100100100
Length To First Branch Height Difference Between Indoor Units > 3 mm8585858585
Equivalent Length Of Outdoor Unit Connecting Pipem1010101010
Real Length Between Single Port FS Unit and Indoor Unit (3 series)m50 (15)50 (15)50 (15)50 (15)50 (15)
Real Length Between Multi Port FS Unit and Indoor Unitm5050505050
Real Length Of Indoor Unit Connecting Pipingm3030303030
Equivalent Length Between Branchesm5050505050
Height Difference Outdoor Higher Than Indoor Unitsm7070707070
Height Difference Outdoor Lower Than Indoor Unitsm3030303030
Height Difference Between Indoor Unitsm4040404040
Height Difference Between Outdoor Unitsm55555
ElectricalVoltage Range Minimum/MaximumV342/456342/456342/456342/456342/456
Electrical Characteristic Run Current Cooling/HeatingA25.1/21.4929.18/24.6827.94/24.8532.41/27.5335.41/30.29
Power Supply Wiring Starting CurrentSoft StartSoft StartSoft StartSoft StartSoft Start
Power SupplyV/ph/Hz380-415/3/50380-415/3/50380-415/3/50380-415/3/50380-415/3/50
Suggested Fused Supply(s)A405025 + 2532 + 2532 + 25

Additional information

3-Pipe Heat Recovery (HP 18 to 26)

AP2216FT8P-UK, AP2416FT8P-UK, AP2616FT8P-UK, MAP1806FT8P-UK, MAP2006FT8P-UK

Reviews

There are no reviews yet.

Be the first to review “3-Pipe Heat Recovery (HP 18 to 26)”

Downloads

No files uploaded.