Description
Combination | MMY- | AP4026HT8P-E | AP4226HT8P-E | AP4426HT8P-E | AP5426HT8P-E | |
Model Name Heat Pump | MMY- | MAP1406HT8P-E MAP1406HT8P-E MAP1206HT8P-E | MAP1406HT8P-E MAP1406HT8P-E MAP1406HT8P-E | MAP1606HT8P-E MAP1406HT8P-E MAP1406HT8P-E | MAP2006HT8P-E MAP2006HT8P-E MAP1406HT8P-E | |
Capacity Range | hp | 40 | 42 | 44 | 54 | |
Maximum Number of Indoor Units | QTY | 64 | 64 | 64 | 64 | |
Cooling Capacity | kW | 113.5 | 120.0 | 125.0 | 152.0 | |
Heating Capacity | kW | 127.5 | 135.0 | 140.0 | 171.0 | |
Operating Range Cooling/Heating | °C | -5.0 to 46.0/-25.0 to 15.5 | -5.0 to 46.0/-25.0 to 15.5 | -5.0 to 46.0/-25.0 to 15.5 | -5.0 to 46.0/-25.0 to 15.5 | |
Cooling | Power Consumption | kW | 34.6 | 36.9 | 38.9 | 46.9 |
EER/SEER/Energy Efficiency Class (or ηsc %) | 3.28/5.80/229.0 | 3.25/5.69/224.6 | 3.21/5.56/219.4 | 3.24/5.74/226.6 | ||
Heating | Power Consumption | kW | 32.1 | 33.6 | 35.3 | 45.2 |
COP/SCOP/Energy Efficiency Class (or ηsc(A) %) | 3.98/3.60/229.0 | 4.02/3.57/224.6 | 3.97/3.62/219.4 | 3.78/3.59/226.6 | ||
Fan(s) | Standard Air Flow H | l/s | 3389 + 3389 + 3389 | 3389 + 3389 + 3389 | 3500 + 3389 + 3389 | 4972 + 4972 + 3389 |
Standard Air Flow H | m3/h | 12200 + 12200 + 12200 | 12200 + 12200 + 12200 | 12600 + 12200 + 12200 | 17900 + 17900 + 12200 | |
External Static Pressure | Pa | 50 | 50 | 40 | 40 | |
Sound | Pressure Level C/H | dB(A) | 64.5/66.5 | 65/67 | 65.5/67.5 | 65.5/67 |
Power Level C/H | dB(A) | 85/87 | 85/87 | 85.5/87.5 | 86.5/88.5 | |
Unit(s) | Height x Width x Depth | mm | 1830 x 3450 x 780 | 1830 x 3670 x 780 | 1830 x 3670 x 780 | 1830 x 4450 x 780 |
Weight | kg | 300 + 300 + 242 | 300 + 300 + 300 | 300 + 300 + 300 | 371 + 371 + 300 | |
Refrigerant Base Charge | kg | 11.5 + 11.5 + 11.5 | 11.5 + 11.5 + 11.5 | 11.5 + 11.5 + 11.5 | 11.5 + 11.5 + 11.5 | |
Pipe Connections | Suction Gas Pipe Brazing | inch | 1-5/8 | 1-5/8 | 1-5/8 | 1-5/8 |
Liquid Pipe Flare | inch | 7/8 | 7/8 | 7/8 | 7/8 | |
Balance Pipe Flare | inch | 3/8 | 3/8 | 3/8 | 3/8 | |
Maximum | Equivalent Length | m | 235 | 235 | 235 | 185 |
Real Length | m | 190 | 190 | 190 | 145 | |
Total Pipe Length (Liquid Line Real Length) | m | 1000 | 1000 | 1000 | 1000 | |
Length To First Branch | m | 100 | 100 | 100 | 100 | |
Equivalent Length Of Outdoor Unit Connecting Pipe | m | 10 | 10 | 10 | 10 | |
Real Length Of Indoor Unit Connecting Piping | m | 30 | 30 | 30 | 30 | |
Equivalent Length Between Branches | m | 50 | 50 | 50 | 50 | |
Height Difference Outdoor Higher Than Indoor Units | m | 70 | 70 | 70 | 70 | |
Height Difference Outdoor Lower Than Indoor Units | m | 40 | 40 | 40 | 40 | |
Height Difference Between Indoor Units | m | 40 | 40 | 40 | 40 | |
Height Difference Between Outdoor Units | m | 5 | 5 | 5 | 5 | |
Electrical | Voltage Range Minimum/Maximum | V | 342/456 | 342/456 | 342/456 | 342/456 |
Electrical Characteristic Run Current Cooling/Heating | A | 54.50/50.60 | 58.50/53.40 | 61.40/55.80 | 73.10/70.00 | |
Power Supply Wiring Starting Current | Soft Start | Soft Start | Soft Start | Soft Start | ||
Power Supply | V/ph/Hz | 380-415/3/50 | 380-415/3/50 | 380-415/3/50 | 380-415/3/50 | |
Suggested Fused Supply(s) | A | 32 + 32 + 25 | 32 + 32 + 32 | 40 + 32 + 32 | 40 + 40 + 32 |