Description
Combination | MMY- | AP2026HT8P-E | AP2226HT8P-E | AP3626HT8P-E | AP3826HT8P-E | |
Model Name Heat Pump | MMY- | MAP1006HT8P-E MAP1006HT8P-E | MAP1206HT8P-E MAP1006HT8P-E | MAP1206HT8P-E MAP1206HT8P-E MAP1206HT8P-E | MAP1406HT8P-E MAP1206HT8P-E MAP1206HT8P-E | |
Capacity Range | hp | 20 | 22 | 36 | 38 | |
Maximum Number of Indoor Units | QTY | 45 | 49 | 64 | 64 | |
Cooling Capacity | kW | 56.0 | 61.5 | 100.5 | 107.0 | |
Heating Capacity | kW | 63.0 | 69.0 | 112.5 | 120.0 | |
Operating Range Cooling/Heating | °C | -5.0 to 46.0/-25.0 to 15.5 | -5.0 to 46.0/-25.0 to 15.5 | -5.0 to 46.0/-25.0 to 15.5 | -5.0 to 46.0/-25.0 to 15.5 | |
Cooling | Power Consumption | kW | 15.4 | 17.7 | 30.0 | 32.3 |
EER/SEER/Energy Efficiency Class (or ηsc %) | 3.64/6.15/243.0 | 3.48/6.11/241.4 | 3.35/6.03/238.2 | 3.31/5.91/233.4 | ||
Heating | Power Consumption | kW | 14.8 | 17.1 | 29.0 | 30.5 |
COP/SCOP/Energy Efficiency Class (or ηsc(A) %) | 4.25/3.54/243.0 | 4.04/3.61/241.4 | 3.89/3.67/238.2 | 3.93/3.63/233.4 | ||
Fan(s) | Standard Air Flow H | l/s | 2694 + 2694 | 3389 + 2694 | 3389 + 3389 + 3389 | 3389 + 3389 + 3389 |
Standard Air Flow H | m3/h | 9700 + 9700 | 12200 + 9700 | 12200 + 12200 + 12200 | 12200 + 12200 + 12200 | |
External Static Pressure | Pa | 60 | 50 | 50 | 50 | |
Sound | Pressure Level C/H | dB(A) | 60/61 | 61.5/63 | 64/66 | 64.5/66.5 |
Power Level C/H | dB(A) | 77/77 | 81/83 | 85/87 | 85/87 | |
Unit(s) | Height x Width x Depth | mm | 1830 x 2000 x 780 | 1830 x 2000 x 780 | 1830 x 3010 x 780 | 1830 x 3230 x 780 |
Weight | kg | 242 + 242 | 242 + 242 | 242 + 242 + 242 | 300 + 242 + 242 | |
Refrigerant Base Charge | kg | 11.5 + 11.5 | 11.5 + 11.5 | 11.5 + 11.5 + 11.5 | 11.5 + 11.5 + 11.5 | |
Pipe Connections | Suction Gas Pipe Brazing | inch | 1-1/8 | 1-1/8 | 1-5/8 | 1-5/8 |
Liquid Pipe Flare | inch | 5/8 | 3/4 | 7/8 | 7/8 | |
Balance Pipe Flare | inch | 3/8 | 3/8 | 3/8 | 3/8 | |
Maximum | Equivalent Length | m | 220 | 220 | 235 | 235 |
Real Length | m | 180 | 180 | 190 | 190 | |
Total Pipe Length (Liquid Line Real Length) | m | 300 | 300 | 1000 | 1000 | |
Length To First Branch | m | 100 | 100 | 100 | 100 | |
Equivalent Length Of Outdoor Unit Connecting Pipe | m | 10 | 10 | 10 | 10 | |
Real Length Of Indoor Unit Connecting Piping | m | 30 | 30 | 30 | 30 | |
Equivalent Length Between Branches | m | 50 | 50 | 50 | 50 | |
Height Difference Outdoor Higher Than Indoor Units | m | 70 | 70 | 70 | 70 | |
Height Difference Outdoor Lower Than Indoor Units | m | 40 | 40 | 40 | 40 | |
Height Difference Between Indoor Units | m | 40 | 40 | 40 | 40 | |
Height Difference Between Outdoor Units | m | 5 | 5 | 5 | 5 | |
Electrical | Voltage Range Minimum/Maximum | V | 342/456 | 342/456 | 342/456 | 342/456 |
Electrical Characteristic Run Current Cooling/Heating | A | 24.20/23.20 | 27.60/26.60 | 46.50/45.00 | 50.50/47.80 | |
Power Supply Wiring Starting Current | Soft Start | Soft Start | Soft Start | Soft Start | ||
Power Supply | V/ph/Hz | 380-415/3/50 | 380-415/3/50 | 380-415/3/50 | 380-415/3/50 | |
Suggested Fused Supply(s) | A | 25 + 25 | 25 + 25 | 25 + 25 + 25 | 32 + 25 + 25 |